HEARTH DIMENSIONS and FIREBOx LOCATION
D
A
Ref.
GCUF32C
A
9M\,"
FP2901
B
13Z\v"
hearth dims
C
3C\,"
D
1M\,"
E
18"
Figure 2 -
Minimum Hearth Dimensions
71D0530
C
E
B
GCUF36C
GCUF42C
34"
40"
15C\v"
15C\v"
7C\,"
33C\,"
1M\,"
1M\,"
17B\,"
17B\,"
LOCATION OF FIREBOx
Carefully select the best location for installation of your
vent-free firebox. The following factors should be taken
into consideration:
Clearance to side wall, ceiling, woodwork and windows.
See "Clearances/Height Requirements on page 8.
Minimum clearances to combustibles must be main-
tained.
Location must not be affected by drafts caused by
kitchen exhaust fans, ceiling fans, return air registers
for forced air furnaces / air conditioners, windows or
doors.
Installation must provide adequate ventilation and com-
bustion air.
DO NOT INSTALL THIS FIREBOx IN A BEDROOM
OR BATHROOM.
Location should be out of high traffic or windy or drafty
areas.
DO NOT INSTALL WHERE CURTAINS, FURNITURE,
CLOTHING OR OTHER FLAMMABLE OBJECTS ARE
LESS THAN 42" FROM FRONT OF HEATER.
Never obstruct the front opening of the vent-free firebox
or restrict the flow of combustion and ventilation air.
Minimize modifications to existing construction. Refer
to Figure 3 below for location suggestions.
Do not install in the vicinity where gasoline or other
flammable liquids may be stored. The vent-free firebox
must be kept clear and free from these combustible
materials.
Figure 3 -
Location of Firebox
FP2440
fireplace locations
GCUF Vent-Free Fireboxes
FP440
7