Samsung EH035CAV Installation Manual page 44

System air conditioner (cooling and heating)
Hide thumbs Also See for EH035CAV:
Table of Contents

Advertisement

Wiring Diagram of Power Cable
When using ELB for 1 phase
Power Supply
MCCB
Electrical component box
ELB
MCCB
Indoor Unit
C C
A A
U U
T T
I I
O O
N N
C C
A A
U U
T T
I I
O O
N N
N You should connect the power cable into the power cable
terminal and fasten it with a clamp.
N The unbalanced power must be maintained within 2% of
supply rating.
- If the power is unbalanced greatly, it may shorten the life
of the condenser. If the unbalanced power is exceeded
over 4% of supply rating, the indoor unit is protected,
stopped and the error mode indicates.
N To protect the product from water and possible shock,
you should keep the power cable and the connection cord
of the indoor and outdoor units in the iron pipe.
N Connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be
incorporated in the fixed wiring(≥3mm).
N Must keep the cable in a protection tube.
N Keep distances of 50mm or more between power cable
and communication cable.
N Outdoor unit
Communication
wire
Connection wire
Cable
clamp
Main power wire
11