WTGO
GOLD
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 —
Install burner — all boilers
Install burner
(also refer to instructions packed with
burner)
Use only burners specified for use on
Weil-McLain GOLD oil boilers. DO
NOT use burners specified for use on
Weil-McLain Model 68 boilers. Contact
individual burner manufacturers for
proper burner selections.
Figure 6
Water boiler controls
Circulator
Relief
valve
Part number 550-141-825/1211
SERVICE TECHNICIAN ONLY — read and follow completely.
For P-WTGO and A-WTGO boiler
1. Secure universal mounting flange and gasket to burner mounting door.
Use three bolts provided.
2. Secure burner on flange with three bolts.
3. Position burner so end of air tube is level to 1½° tilt downward. Open
door to verify burner position. End of air tube should be flush to ¼"
recessed from inside wall of burner door refractory. Check for secure
placement of insulation on target wall, chamber floor and burner
mounting door. Securely close door with nut.
Boiler Manual
Water
pressure-temperature
gauge
Combination
Limit control
and low water
cut-off
Drain valve
15