CONNECTION DIAGRAM AND TERMINAL
REMARKS
1. As the input signals are at low level, use two parallel micro signal contacts or a twin contact for relay contact
inputs to prevent a contact fault.
2. A transistor of the following specifications should be selected for the open collector signal:
Electrical characteristics of the transistor used
⋅ I
≥ 10mA
c
⋅ Leakage current: 100
⋅ V
≥ 30V
CE
⋅ If I
≥ 10mA, V
c
CE (sat)
10
Micro signal contacts
µ
A maximum
voltage is 3V maximum
Twin contacts