Safety Precautions - Liebert ITA UPS 16kVA User Manual

Ita ups 16kva/20kva
Table of Contents

Advertisement

Safety Precautions

This manual contains the information concerning the installation and operation of Liebert ITA 16kVA/20kVA UPS
(hereinafter referred to as UPS).
Please carefully read this manual prior to installation.
The UPS must be installed, commissioned and serviced by engineers designated by the manufacturer or its
agent. Failure to observe this could result in personnel safety risk, UPS malfunction and invalidation of warranty.
The UPS has been designed for commercial and industrial use only, and is not recommended for use in life
support applications.
This is a Class A UPS product. In a residential environment, this product may nevertheless cause radio
interference, in which case, the user may be required to take additional measures.
The UPS complies with 2006/95/EC, 93/68/EEC (LV Safety) and 2004/108/EC (EMC), with Australia and New Zealand EMC
Framework (C-Tick) and with the following product standards for UPS:
* IEC62040-1-1: General and safety requirements for use in operator access area
* IEC62040-2: EMC requirements, Class C2 compliant
* IEC62040-3: Performance requirements and test methods
The UPS installation should follow the above instructions and use the accessories specified by manufacturer.
Earth connection is essential before connecting the input power supply (AC mains and battery included). This equipment
must be earthed in accordance with the local electrical codes.
Earth leakage current ranges from 3.5mA to 1000mA.
Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into
account when selecting instantaneous residual current circuit breaker (RCCB) or residual current detector (RCD) devices.
RCCB must be selected, for it is insensitive to DC unidirectional pulses (Class A) and transient current pulses.
Note that the earth leakage currents of the load will be carried by RCCB or RCD.
The UPS has a zero-voltage contact closure signal available for use with an external automatic circuit breaker (single power
supply), to protect against backfeeding voltage through the static bypass circuit. If the installing engineer do not need to use
this signal, a label must be added to the switchgear to advise service personnel that the circuit is connected to a UPS
system.
The text can be written: ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
All equipment maintenance and servicing procedures involve internal should be carried out only by trained personnel.
Removal of devices behind the protective cover requires the use of a tool and is restricted to service personnel.
The UPS meets the safety requirements completely in operator access area. Only the service personnel can contact with the
hazardous voltage inside the UPS. However, the risk of contacting with these voltages is minimized as the components with
hazardous voltage may be contacted only uses a tool to remove the protective cover. No risk exists to any personnel when
operating the equipment in normal manner, following the recommended operation procedures.
Conformity and standards
Warning: High Leakage Current
Warning: Reflected Protection
Maintainable Components