Checking Gas Connections - Desa Glo-Warm FA-20BB Owner's Operation And Installation Manual

Glo-warm blue flame vent-free natural gas heater
Hide thumbs Also See for Glo-Warm FA-20BB:
Table of Contents

Advertisement

BLUE FLAME NATURAL GAS HEATER
INSTALLATION
Continued
CHECKING GAS
CONNECTIONS
WARNING: Test all gas pip-
ing and connections for leaks
after installation or servicing.
Correct all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
Pressure Testing Gas Supply
Piping System
Test Pressures In Excess Of 1/2 PSIG
(3.5 K Pa)
1. Disconnect heater and its individual
manual shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig will damage heater regulator.
2.
Cap off open end of gas pipe where
manual shutoff valve was connected.
3. Pressurize supply piping system by ei-
ther using compressed air or opening
main gas valve located on or near gas
meter.
4. Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
5. Correct all leaks at once.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 K Pa)
1. Close manual shutoff valve (see Fig-
ure 13).
2. Pressurize supply piping system by ei-
ther using compressed air or opening
main gas valve located on or near gas
meter.
3. Check all joints from gas meter to
manual shutoff valve (see Figure 14).
Apply mixture of liquid soap and wa-
ter to gas joints. Bubbles forming show
a leak.
4. Correct all leaks at once.
Manual
Shutoff
Valve
Figure 13 - Manual Shutoff Valve
Gas Meter
Figure 14 - Checking Gas Joints
10
Pressure Testing Heater Gas
Connections
1.
Open manual shutoff valve (see Fig-
ure 13).
2.
Open main gas valve located on or near
gas meter.
3.
Make sure control knob of heater is in
the OFF position.
4.
Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 14). Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
5.
Correct all leaks at once.
6.
Light heater (see Operating Heater,
pages 11 and 12 for thermostat models
Open
ON
or pages 12 and 13 for non-thermostat
POSIT
models). Check all other internal joints
for leaks.
7.
Turn off heater (see To Turn Off Gas
to Appliance, page 12 for thermostat
models or page 13 for non-thermostat
O
Closed
POS
models).
8.
Replace front panel.
Gas Valve
Manual
Shutoff Valve
105568