SYMPTOM
PROBLEM
Exhaust fumes
Fireplace is spilling.
smelled in room,
headaches.
Pilot will not light.
Wiring.
Makes noise with
no spark at pilot
burner.
Loose connection.
Igniter Spark gap is
incorrect.
Pilot will not light.
A shorted or loose
Makes no noise
connection.
with no spark at
pilot burner.
Crystalites™ and
blower operates.
Module is not grounded.
Ignition box has been
locked out.
NOTE: Starting from OFF, press the ON button on the transmitter. Approximately 4
seconds after the ON/OFF button is pressed the ignition board will start the spark. The
first try for ignition will last approximately 60 seconds. If there is no flame ignition
(rectification) the board will stop sparking for approximately 35 seconds. After the wait
time the board will start the second try for ignition by sparking for approximately 60
seconds. If there is still no positive ignition, the board will go into lock out.
TEST SOLUTION
- Ensure exhaust bracket gasket seal.
- Check door seal.
- Check for exhaust blockage.
- Check that venting is installed correctly.
- Room is in negative pressure; increase fresh air supply.
- Verify the wire for the sensor and the wire for the ignitor
are connected to the correct terminals (not reverse) on
the module and pilot assembly.
- Verify no loose connections, electrical shorts in the
wiring or ground out to any metal object.
- Spark gap of the ignitor to the pilot should be .125"
(1/8").
- Remove and reinstall the wiring harness that plugs into
the module.
- Remove and verify continuity of each wire in the wiring
harness.
- Verify the valve and pilot assemblies are properly
grounded to the metal chassis of the fireplace.
Choose one of the 4 methods below to reset the system.
1. To reset ignition box when locked out. Turn off power supply
and remove batteries (if used) from the receiver.
2. To reset the DFC Board when the board goes into a lock out
condition and the LED is blinking 3 times using the transmitter
ON/OFF button:
Step 1: Turn the system off by pressing the ON/OFF
button to turn the system off.
Step 2: After approximately 2 seconds press the
ON/OFF button on the transmitter again. THE DFC
Board will reset and the ignition sequence will start
again.
3. To reset the DFC Board when the board goes into a lock out
condition and the LED is blinking 3 times by cycling flame:
Step 1: In the manual flame control mode, use the down
arrow button to reduce the flame to off, indicated by the
word OFF displayed on the trasmitter LCD screen.
Step 2: Wait approximately 2 seconds and press the up
arrow button, the ignition sequence will start.
4. To reset the DFC Board when the board goes into a lock out
condition and the LED is blinking 3 times using the receiver
switch.
Step 1: With the transmitter off, move the slider switch
on the receiver to the OFF position.
Step 2: Wait approximately 2 seconds and move the
receiver slider switch to the ON position. The ignition
sequence will start again.
55