Trane 18-HD64D1-4 Installation Manual page 13

Comfortlink ii
Table of Contents

Advertisement

Installer Setup Menus and Options (continued)
Menu
5.2.6 ADVANCED
SENSORS
5.2.7 ADVANCED
ZONING
Please refer to the Zone Panel Installer's Guide for detailed information.
18-HD64D1-4
Setting
 Select Outdoor Temperature Sensor................................................ None
 Calibrate Outdoor Temperature Sensor - Degrees .......................... +/- in 5° Increments
 Calibrate Indoor Temperature Sensor - Degrees ............................. Zone X in +/- 5° Increments
 Calibrate RH Sensor ........................................................................ Zone X in +/- 5° Increments
Thermostat Humidity Sensor ........................................................... Disable
 Damper Travel Time ......................................................................... 15 - 60 Seconds
 Auto Detect Damper ........................................................................ No, Yes
 Detected Dampers ........................................................................... 2 - 8
 Run Auto Zone Airflow Capacity ...................................................... No, Yes
 Auto Zone Airflow Capacity Adjustment ........................................... Normal
 Airflow Capacity - % of Total ............................................................ 25% - 100%
 Voting Zones .................................................................................... No, Yes
 Indoor Heating Airflow Offset % (above and below cooling airflow) . -50 - +50, 0
 Discharge Temperature Limit - Cooling ............................................ Normal (38), Extended (34)
 Discharge Temperature Limit - Compressor Heating Only ............... Normal (116), Extended (128)
 Discharge Temperature Limit - Compressor Heating w/Aux Heat .... Normal (160), Extended (170)
 Heating Fuel Type ............................................................................ Gas
 Discharge Temperature Limit - Gas Furnace Heating ...................... Normal (135), Extended (145)
 Discharge Temperature Limit - Oil Furnace Heating ........................ Normal (160), Extended (170)
 Discharge Temperature Limit - Hydronic Heating ............................ Normal (135), Extended (145)
Available Options
Sensor Wired to Control
CLII/AccuLink Outdoor Sensor
Sensor Wired to Relay Panel
Enable
More Aggressive
Less Aggressive
Oil