15.4. Error Codes Table

Diagnosis
Abnormality / Protection control
display
H00
No abnormality detected
H11
Indoor / outdoor abnormal
communication
H12
Connection capability rank abnormal
H14
Indoor intake air temperature sensor
abnormality
H15
Outdoor compressor temperature sensor
abnormality
H16
Outdoor Current Transformer open
circuit
H19
Indoor fan motor merchanism lock
H23
Indoor heat exchanger temperature
sensor abnormality
H25
E-Ion breakdown
H27
Outdoor air temperature sensor
abnormality
H28
Outdoor heat exchanger temperature
sensor abnormality
H30
Discharge temperature sensor
abnormality
H33
Indoor/Outdoor wrong connection
H38
Indoor/Outdoor mismatch
H58
Abnormal gas sensor
H97
Outdoor Fan Motor lock abnormality
H98
Indoor high pressure protection
H99
Indoor heat exchanger anti-freezing
protection
F11
Cooling / Heating cycle changeover
abnormality
F90
PFC control
F91
Refrigeration cycle abnormality
F93
Outdoor compressor abnormal revolution
F95
Cool high pressure protection
F96
IPM (power transistor) overheating
protection
F97
Outdoor compressor overheating
protection
F98
Total running current protection
F99
Outdoor Direct Current (DC) peak
detection
Note:
"O" - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until "beep" sound heard
following by pressing the "CHECK" button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one "beep" to four "beep" sounds.
Abnormality
Emergency
Judgement
operation
Normal operation
> 1 min after starting
Indoor fan operation
operation
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
(Cooling only)
Continue for 5 sec.
Continue for 5 sec.
Continue for 6 hours
4 times occurance
within 30 minutes
4 times occurance
within 10 minutes
7 times occurance
continuously
4 times occurance
within 20 minutes
4 times occurance
within 20 minutes
4 times occurance
within 20 minutes
3 times occurance
within 20 minutes
7 times occurance
continuously
56
Primary location to verify
• Internal / external cable connections
only
• Indoor / Outdoor PCB
• Intake air temperature sensor
(defective or disconnected)
• Compressor temperature sensor
(defective or disconnected)
• Outdoor PCB
• IPM (Power transistor) module
• Indoor PCB
• Fan motor
O
• Heat exchanger temperature sensor
(defective or disconnected)
• Indoor PCB
• E-Ion PCB
O
• Outdoor temperature sensor (defective
or disconnected)
O
• Outdoor heat exchanger temperature
sensor (defective or disconnected)
• Indoor/Outdoor supply voltage
• Gas sensor
(defective or disconnected)
• Outdoor PCB
• Outdoor Fan Motor
• Air filter dirty
• Air circulation short circuit
• Insufficient refrigerant
• Air filter dirty
• 4-way valve
• V-coil
• Voltage at PFC
• No refrigerant
(3-way valve is closed)
• Outdoor compressor
• Outdoor refrigerant circuit
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
• Insufficient refrigerant
• Compressor
• Excess refrigerant
• Improper heat radiation
• Outdoor PCB
• IPM (Power transistor)
• Compressor