Shrouds
A. HHT Shrouds
•
You may install a shroud with this fi replace. See Section 17.D. for a list of UL Listed shrouds. Follow the instructions
included with these optional components
B. Field Constructed Shrouds
WARNING! Risk of Fire! Shrouds must be constructed
as specifi ed. Improper construction may overheat chase
top.
•
Chase top shrouds may be fi eld constructed where permitted by regional building codes.
NOTICE: Some regional codes require an agency-Listed
shroud. Consult your local building offi cials.
•
The following fi eld constructed shroud designs have been tested for Hearth Technologies fi replace systems and termination
caps.
•
The shrouds must be constructed from a minimum .018 in. (26 ga) thick aluminized steel.
•
The wire mesh is optional but recommended and must be .018 in. thick minimum, 1/2 in. mesh.
Open Top Shroud (may be used with DVP-TV, DVP-TVHW, SLP-TVHW)
Min.
Top Dim.
Min.
Top Dim.
Min.
Base Dim.
Figure 11.1 Open Top Shroud Dimensions
Min.
Base Dim.
Heatilator • Novus NNXT • 4055-879 • Rev E • 5/10
Min. Base Dims.
in
19 x 19
mm
483 x 483
Min. Top Dims.
in
16 x 16
mm
406 x 406
47