Download Print this page

American Water Heater 701022 Owner's Manual

American water heater indoor gas water heater owner's manual

Advertisement

Quick Links

Controller
In Use Indicator
Indicates that hot water
is being supplied.
Priority Indicator
Indicates that this
controller is setting the
Temperature Display
water temperature.
Indicates temperature
setting or flashes error
Priority Button
code.
When no water is
being supplied,
pressing this button
Thermostat
allows this controller to
set the water
temperature.
ON/OFF Button
Diagnostic Use of the Controller
1. To display error codes, press the ON/OFF button followed by
the
thermostat button to cycle through the error codes.
2. To display the water flow through the water heater, press the
thermostat button (hold for 2 seconds) and then press the
ON/OFF button while continuing to hold the
thermostat
button.
3. To display the outlet water temperature, press the
button (hold for 2 seconds) and then press the ON/OFF button
while continuing to hold the
thermostat button.
To Change the Temperature Scale (ºF / ºC)
With the water heater turned off, press and hold the ON/OFF
button until the display changes to the other temperature scale
(about 5 seconds).
To Turn Off the Controller Sound (Mute)
To turn the sound off (mute), press and hold both the
thermostat buttons until a "beep" is heard (about 5 seconds).

Gas Pressure Setting

NOTE: For additional installation and commissioning information refer
to the Operation and Installation Manual.
WARNING
This appliance must be installed, serviced and removed by a trained
and qualified person. During pressure testing of the consumer piping,
ensure gas valve is turned off before unit is shut off. Failure to do so
may result in serious injury to yourself or damage to the unit.
APPLIANCE OPERATING PRESSURES
Table 1
Gas Inlet
Forced Low
Water
Min./Max
Inlet Max.
NAT.G
LPG
NAT.G
LPG
705(Indoor)
5"W.C.
8"W.C.
1
5
0
P
I S
0
6 .
" 7
W
.
. C
0
8 .
" 3
W
.
. C
/10.5"W.C.
/13.5"W.C.
705(Indoor-ASME)
Commissioning
With all gas appliances in operation at maximum gas rate, the
flowing inlet pressure at the incoming test point on the Rinnai
water heater should read 5" W.C. - 10.5" W.C. on natural gas
and 8" W.C. - 13.5" W.C. on propane gas. If the pressure is
lower, the gas supply is inadequate and the unit will not operate
to specification. Check the gas meter regulator and pipework for
correct operation/sizing and correct as required.

Troubleshooting

Important Safety Notes
There are a number of (live) tests that are required when fault
finding this product. Extreme care should be used at all times to
avoid contact with energized components inside the water heater.
Only trained and qualified service technicians should attempt to
repair this product. Before checking for resistance readings,
disconnect the power source to the unit and isolate the item from
the circuit (unplug it).
(SV1, SV2, SV3 and POV) Gas valve and Modulating solenoids: (Set meter above 2K)
Wire color
Voltage
Resistance
Connector #
(Main) Pink - Black
11 ~ 13 VDC
24 ~ 28 ohms
H3
(SV1) Black - Red
11 ~ 13 VDC
37 ~ 43 ohms
H4
(SV2) Black - Orange 11 ~ 13 VDC
37 ~ 43 ohms
H5
(SV3) Black - Yellow
11 ~ 13 VDC
37 ~ 43 ohms
H6
(POV) Orange - Orange 2 ~ 15 VDC
67 ~ 81 ohms
H2
(M) Water Flow Control Device Servo or Geared Motor:
Red - Blue
11 ~ 13 VDC
22 ~ 28 ohms
F5
Grey - Brown
4 ~ 6 VDC
N / A
F5
Grey - Yellow
N / A
N / A
F5
NOTE: The grey wire listed above turns to black at F connector on the PCB.
(QS) Water Flow Sensor:
Black - Red
11 ~ 13 VDC
5.5 ~ 6.2 K ohms
F2
Yellow - Black
4 ~ 7 VDC
1 ~ 1.4 Mega ohms F2
By-pass Flow Control:
r B
w o
- n
W
h
e t i
G
1
Orange - White
2 ~ 6 VDC
G1
15 ~ 35 ohms
Yellow - White
G1
(Unit in operating mode)
R
d e
W -
t i h
- e
r G
u o
d n
G
1
(IG) Ignition System:
Grey - Grey
90 ~ 110 VAC
N / A
C1
(FM) Combustion Fan Motor:
Red - Black
6 ~ 45 VDC
N / A
E1
White - Black
5 ~ 10 VDC
9.2 ~ 9.4 K ohms
E1
Yellow - Black
11 ~ 13 VDC
3.5 ~ 3.9 K ohms
E1
Set your meter to the hertz scale. Reading across the white and black wires at terminals 2 and 4
you should read between 60 and 420 hertz.
Thermal Fuse / Overheat Switch:
F6
Red - White
11 ~ 13 VDC
Below 1 ohms
H1
Flame Rod:
Place one lead of your meter to the flame rod and the other to ground.
With the unit running you should read between 5-150 VAC. Set your
meter to the µ amp scale and series your meter in line with the flame
rod. You should read 1 µ amp or greater for proper flame circuit. In
the event of low flame circuit remove the flame rod and check for
carbon or damage.
Dip Switches Settings
Adjust switches 2 and 3 in the bank of 8 depending on
your altitude according to the table below.
The original PC boards on the water heaters do not
have the bank of 6 dip switches. Only spare PC
boards have this bank.
High Altitude
SW
No.
Level 0
2
Off
High Altitude
0-2000 ft
3
Off
(0-610 m)
Gas Pressure Setting
Ensure gas pressure check under Commissioning has been
completed first! The regulator is electronically controlled and
factory pre-set. Under normal circumstances it does not require
adjustment during installation. Make adjustments only if the unit is
not operating correctly and all other possible causes for incorrect
operation have been eliminated.
1. Turn OFF the gas supply.
2. Turn OFF the 120 V power supply.
3. Remove the front panel from the appliance.
4. Check the gas type using the data plate on the side of the unit.
If using a spare PC board, check that the gas type switches are
in the correct position (dip switch 1 of SW2: ON for natural gas,
NG, and OFF for propane, LPG). See dip switch settings
section below. (ON is towards the right and OFF is towards the
left.)
5. Attach the pressure gauge to the burner test point, located on
the gas control (Fig. 2).
6. Turn ON the gas supply.
7. Turn ON the 120 V power supply.
8. If a controller is installed, turn the unit ON with the controller.
Select the maximum delivery temperature and open all
available hot water taps at full.
9. Set the unit to 'Forced Low' combustion by setting No. 7 dip
switch of the SW1 set to ON (Fig. 3).
10. Check the burner test point pressure.
thermostat
11. Remove the rubber access plug and adjust the regulator screw
on the modulating valve (Fig. 4) as required in Table 1.
Replace the rubber access plug.
12. Set the unit to 'Forced High' combustion by setting both No. 7
and No. 8 dip switches of the SW1 set to ON (Fig. 5). Ensure
maximum water flow.
13. Check the burner test point pressure.
14. Adjust the high pressure potentiometer (POT) on the PC board
as required to the pressure shown in Table 1.
15. Return the unit to normal operation by setting dip switches 7
and 8 of the SW1 set back to OFF (Fig. 6). Close all water
taps.
and
16. Turn OFF the gas supply and 120 V power supply.
17. Remove the pressure gauge and install sealing screw.
18. Turn ON the gas supply and 120 V power supply.
19. Operate the unit and check for gas leaks at the test point.
20. Install the front panel.
High Pressure
Potentiometer
Burner
test point
SW1
1
SW2
Spare Parts
Only
Fig. 1
Forced High
NAT.G
LPG
. 3
" 0
W
.
. C
. 3
" 7
W
.
. C
Fig. 3
Fig. 5
Heat Exchanger and Outgoing Water Temperature
Thermistors:
Check all thermistors by inserting meter leads into each end of the
thermistor plug. Set your meter to the 20 K scale and read
resistance. Applying heat to the thermistor bulb should decrease
the resistance. Applying ice to the thermistor bulb should increase
the resistance. See below for examples of typical temperatures and
resistance readings.
Example:
59°F = 11.4 ~ 14K
86°F = 6.4 ~ 7.8K
113°F = 3.6 ~ 4.5K
Outgoing Water Thermistor:
Pin #'s
6 - 7
White - White
N / A
See example above F4
5 - 6
Heat Exchanger Temperature Thermistor:
4 - 6
Pink - White
N / A
See example above F3
3 - 6
9 - 10
Surge Protector:
Black - White
108 ~ 132 VAC
N / A
Black - White
108 ~ 132 VAC
N / A
9 - 10
With the power off you can check the continuity through the surge
5 - 7
5 - 8
protector. Place a meter lead on the top pin #1 of the surge
protector and pin #3 on the bottom of the surge protector. Check
across the top pin #3 and bottom pin #1. If you read continuity
across these two points then the surge protector is good. If you do
1 - 3
not get continuity then replace the surge protector.
2 - 3
Remote Controls:
Terminals B1
10 ~ 13 VDC
1.5 ~ 3.0 K ohms
1
5 -
2 - 5
Frost Protection:
3 - 5
4
5 -
This unit has frost protection heaters mounted at different points to
protect the water heater from freezing. The heaters located on the
hot water outlet line should have a resistance reading of 180-207
1 - 2
ohms through each of these heaters. The heater located on the
heat exchanger piping should have a resistance reading of 156-180
1 - 2
ohms and the one located in the water flow sensor valve should
2 - 4
have a resistance reading 24-28 ohms.
2 - 3
Amp Fuses:
This unit has one inline (3) amp glass fuses. Remove the fuse and
check continuity through it. If you have continuity through the fuse
F6 - H12
then it is good. Otherwise the fuse is blown and must be replaced.
705(Indoor)
705(Indoor-ASME)
LPG
NAT.G
ON
ON
O
O
1
1
F
2
F
2
3
3
F
F
4
4
5
5
6
6
7
7
8
8
ON
ON
O
O
1
1
F
2
F
2
3
3
F
F
4
4
5
5
6
6
WARNING
DO NOT adjust the other dip switches unless specifically instructed
to do so. Incorrect Dip Switch Settings can cause the water heater
to operate in an unsafe condition and may damage the water heater
and void the warranty.
NOTES
Level 1
Level 2
Off
On
On
2001-5200 ft
5201-7700 ft
On
Off
On
(610-1585 m)
(1585-2347 m)
No burner operation during freeze protection mode
02
Service Call
03
Power interruption during Bath fill (Water will not flow when
power returns)
Turn off all hot water taps. Press ON/OFF twice.
Air Supply or Exhaust Blockage
10
Ensure approved venting materials are being used.
Check that nothing is blocking the flue inlet or exhaust.
Check all vent components for proper connections.
Ensure vent length is within limits.
Ensure condensation collar was installed correctly.
Verify dip switches are set properly.
Check fan for blockage.
11
No Ignition
Check that the gas is turned on at the water heater, gas meter,
or cylinder.
Ensure gas type and pressure is correct.
Ensure gas line, meter, and/or regulator is sized properly.
Bleed all air from gas lines.
Verify dip switches are set properly.
Ensure appliance is properly grounded.
Disconnect multi-unit connections to isolate the problem.
Ensure igniter is operational.
Check igniter wiring harness for damage.
Check gas solenoid valves for open or short circuits.
Remove burner cover and ensure all burners are properly
seated.
Remove burner plate and inspect burner surface for
condensation or debris.
12
Flame Failure
Check that the gas is turned on at the water heater and gas
meter. Check for obstructions in the flue outlet.
Ensure gas line, meter, and/or regulator is sized properly.
Ensure gas type and pressure is correct.
Bleed all air from gas lines.
Ensure proper venting material was installed.
Ensure condensation collar was installed properly.
Ensure vent length is within limits.
Verify dip switches are set properly.
Ensure appliance is properly grounded.
Disconnect keypad.
Disconnect multi-unit connections to isolate the problem.
Check power supply for loose connections.
Check power supply for proper voltage and voltage drops.
Ensure flame rod wire is connected.
Check flame rod for carbon build-up.
Disconnect and re-connect all wiring harnesses on unit and PC
Fig. 2
board.
Check all components for electrical short.
Check gas solenoid valves for open or short circuits.
Remove burner plate and inspect burner surface for
condensation or debris.
14
Thermal Fuse
Regulator adjustment
screw access plug
Check gas type of unit and ensure it matches gas type being
used.
Fig. 4
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-
cycling.
Ensure dip switches are set to the proper position.
Check for foreign materials in combustion chamber and/or
exhaust piping.
Fig. 6
Check heat exchanger for cracks and/or separations.
Check heat exchanger surface for hot spots which indicate
blockage due to scale build up. Refer to instructions in manual
for flushing heat exchanger.
Measure resistance of safety circuit.
Ensure high fire and low fire manifold pressure is correct.
Check for improper conversion of product.
140°F = 2.2 ~ 2.7K
221°F = 0.6 ~ 0.8K
3 - 4
3 - 11
D2
1 - 3
D1
1 - 3
B
1 - 3
Level 3
7701-10200 ft
(2347-3109 m)

Error Codes

16
Over Temperature Warning
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-
cycling.
Check for foreign materials in combustion chamber and/or
exhaust piping.
Check for clogged heat exchanger.
Outgoing Water Temperature Sensor Fault
32
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build up.
Replace sensor.
33
Heat Exchanger Outgoing Temperature Sensor Fault
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build up.
Replace sensor.
Combustion Air Temperature Sensor Fault
34
Check for restrictions in air flow around unit and vent terminal.
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build up.
Ensure fan blade is tight on motor shaft and is in good
condition.
Replace sensor.
52
Modulating Solenoid Valve Signal Abnormal
Check modulating gas solenoid valve wiring harness for loose
or damage terminals.
Measure resistance of valve coil.
61
Combustion Fan Failure
Ensure fan will turn freely.
Check wiring harness to motor for damaged and/or loose
connections.
Measure resistance of motor winding.
Water Flow Servo Faulty (does not stop flow properly)
65
If blank screen is present on remote control then the flow control
has shorted out. Unplug flow control. If remote lights up and unit
starts operating then replace flow control assembly.
71
SV0, SV1, SV2, and SV3 Solenoid Valve Circuit Fault
Check wiring harness to all solenoids for damage and/or loose
connections.
Measure resistance of each solenoid valve coil.
72
Flame Sensing Device Fault
Ensure flame rod is touching flame when unit fires.
Check all wiring to flame rod for damage.
Remove flame rod and check for carbon build-up; clean with
sand paper.
Check inside burner chamber for any foreign material blocking
flame at flame rod.
Measure micro amp output of sensor circuit with flame present.
Replace flame rod.
LC
Scale Build-up in Heat Exchanger (when checking
maintenance code history "00" is substituted for "LC")
Flush heat exchanger. Refer to instructions in manual.
Replace heat exchanger.
No Code (Nothing happens when water flow is activated.)
Clean inlet water supply filter.
On new installations ensure hot and cold water lines are not
reversed.
Check for bleed over. Isolate unit from building by turning off
hot water line to building. Isolate the circulating system if
present. Open your pressure relief valve; if unit fires, there is
bleed over in your plumbing.
Ensure you have at least the minimum flow rate required to fire
unit.
Ensure turbine spins freely.
Measure the resistance of the water flow control sensor.
Remote control does not light up but you have 12 VDC at the
terminals for controls.

Wiring Diagram

070 00012 36676 0
705 Indoor
U273-1373(01)

Advertisement

loading

Summary of Contents for American Water Heater 701022

  • Page 1: Error Codes

    Gas Pressure Setting Controller Ensure gas pressure check under Commissioning has been completed first! The regulator is electronically controlled and In Use Indicator factory pre-set. Under normal circumstances it does not require Indicates that hot water adjustment during installation. Make adjustments only if the unit is is being supplied.
  • Page 2 EXPLODED VIEW - CABINET REMOTE CONTROLLER EXPLODED VIEW - INTERNALS Quantity (Indoor) Number Description Parts Number Casing Assembly 701022-150 Heat Protection Plate 701022-154 Front Panel Assembly 701022-155 Remote Controller Packing 701022-159 Wall Fitting Bracket 701022-160 Front Panel Packing-Top 701022-162 Front Panel Packing-Side...

This manual is also suitable for:

705U273-1373(01)