QuickSpecs

Technical Specifications

System Unit Rack
Dimensions (H x W x D)
(with bezel)
Weight
(approximate)
Input Requirements
(per power supply)
BTU Rating
Power Specifications
Power Supply Output
(per power supply)
System Inlet
Temperature
Relative Humidity
(non-condensing)
Altitude
DA - 12770 Worldwide QuickSpecs — Version 18 — 7.18.2008
6.94 x 19.0 x 26.5 in (17.6 x 48.3 x 67.3 cm)
Maximum
(all hard drives, power
supplies, and processors
installed)
Minimum
(one hard drive, power
supply, and processor
installed)
Rated Line Voltage
Rated Input Current
Rated Input Frequency
Rated Input Power
Maximum
To review typical system power ratings use the Power Calculator which
is available via the online tool located at URL:
http://h30099.www3.hp.com/configurator/calc/Power%20
Calculator%20Catalog.xls
- Click on the system of interest. Example: DL580 G5
- Follow the instructions of the next screens.
Rated Steady-State
Power
Maximum Peak Power
Operating
Non-operating
Operating
Non-operating
Operating
HP ProLiant DL580 Generation 5
100.0 lb (45.4 kg)
71.0 lb (32.2 kg)
90 - 132 VAC,
180 - 264 VAC
10 A (at 100 VAC),
7.8 A (at 200 VAC)
47 to 63 Hz
964 W (at 100 VAC),
1412 W (at 240 VAC)
3355 BTU/hr (at 100 VAC),
4914 BTU/hr (at 200 VAC)
800 W (at 100 VAC),
1200 W (at 200 VAC)
800 W (at 100 VAC),
1200 W (at 200 VAC)
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change
is 10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed.
System performance may be reduced if
operating with a fan fault or above 30°C
(86°F).
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
10 to 90% relative humidity (Rh), 28°C
(82.4°F) maximum wet bulb temperature, non-
condensing.
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature,
non-condensing.
3050 m (10,000 ft). This value may be limited
by the type and number of options installed.
Maximum allowable altitude change rate is
457 m/min (1500 ft/min).
Page 44