Reducing Wall And Ceiling Clearances Safely; Shield Construction Rules - Drolet Eastwood 1800 Installation And Operation Manual

Us environmental protection agency phase ii certified wood stove
Hide thumbs Also See for Eastwood 1800:
Table of Contents

Advertisement

Eastwood 1800 Installation and Operation Manual

8.4 Reducing Wall and Ceiling Clearances Safely

It is often desirable to reduce
the
minimum
clearances by placing the stove
closer to walls so the installation
takes up less floor space. You
can safely reduce the minimum
clearances
by
installing a shield between the
stove and combustible material.
The rules for safe shields can be
complicated,
so
carefully
and
follow
exactly. Note that there may be
minor regional differences in
clearance reduction rules so be
sure to check with your building
or
fire
inspector
proceeding.

8.4.1 Shield Construction Rules

1. Minimum space behind shield: 25 mm (1 in.). In Canada 21 mm (7/8 in).
2. Minimum clearance along the bottom of shield: 25 mm (1 in.).
3. Maximum clearance along the bottom of shield: 75 mm (3 in.).
4. Minimum clearance along the top of shield at ceiling: 75 mm (3 in.).
5. Shield extension beyond each side of appliance: 450 mm (18 in.).
6. Shield extension above appliance: 500 mm (20 in.).
7. Edge clearance for ceiling shields: 75 mm (3 in.).
8. Adhesives used in shield construction must not ignite or lose adhesive qualities at
temperatures likely to be encountered.
9. Mounting hardware must allow full vertical ventilation.
10. Mounting hardware must not be located closer than 200 mm (8 in.) from the vertical
centre line of the appliance.
11. Mounting hardware which extends from the shield surface into combustibles may be
used only at the edges of the shield.
installation
permanently
read
them
them
before
31