Gas Supply - American Water Heater 6510381 Installation Instructions And Use & Care Manual

Gas water heater with the flame guard safety system
Table of Contents

Advertisement

Gas Supply

Explosion Hazard
Use a new CSA approved gas supply line.
Install a shut-off valve.
Do not connect a natural gas water
heater to an L.P. gas supply.
Do not connect an L.P. gas water heater
to a natural gas supply.
Failure to follow these instructions can
result in death, explosion, or carbon
monoxide poisoning.
Gas Requirements
Read the data plate to be sure the water heater is made
for the type of gas you will be using in your home. This
information will be found on the data plate located near the
gas control valve/thermostat. If the information does not
agree with the type of gas available, do not install or light.
Call your dealer.
Note: An odorant is added by the gas supplier to the gas
used by this water heater. This odorant may fade over an
extended period of time. Do not depend upon this odorant
as an indication of leaking gas.
Gas Piping
The gas piping must be installed according to all local and
state codes or, in the absence of local and state codes, the
"National Fuel Gas Code", ANSI Z223.1(NFPA 54)-latest
edition.
Table 1 on page 7 provides a sizing reference for commonly
used gas pipe materials. Consult the "National Fuel Gas
Code" for the recommended gas pipe size of other materials.
Refer to Figure 3
Note: When installing gas piping, apply approved pipe joint
compound.
1. Install a readily accessible manual shut-off valve in the
gas supply line as recommended by the local utility.
Know the location of this valve and how to turn off the
gas to this unit.
2. Install a drip leg (if not already incorporated as part of
the water heater) as shown. The drip leg must be no
less than three inches long for the accumulation of dirt,
foreign material, and water droplets.
6
3. Install a ground joint union between the gas valve/
thermostat and the manual shut-off valve. This is to
allow easy removal of the gas valve/ thermostat.
4. Turn the gas supply on and check for leaks. Test the
water heater by brushing on an approved noncorrosive
leak detection solution. Bubbles forming indicate a
leak. Correct any leak found.
Figure 3
Gas Piping
Manual Gas
Shut-off Valve
Ground
Joint
Union
Check with
local utility
for minimum height
3" minimum
Drip leg
Gas Pressure
Important: The gas supply pressure must not exceed the
maximum supply pressure as stated on the water heater's
data plate. The minimum supply pressure is for the purpose
of input adjustment.
Gas Pressure Testing
Important: This water heater and its gas connection must
be leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a
pressure exceeding 14" W.C., the water heater and its
manual shut-off valve must be disconnected from the
gas supply piping system and the line capped.
If the gas lines are to be tested at a pressure less than
14" W.C., the water heater must be isolated from the
gas supply piping system by closing its manual shut-off
valve.
U.L. recognized fuel gas and carbon monoxide (CO)
detectors are recommended in all applications and should
be installed using the manufacturer's instructions and local
codes, rules, or regulations.
Note: Air may be present in the gas lines and could prevent
the pilot from lighting on initial start-up. The gas lines
should be purged of air by a qualified service technician
after installation of the gas piping system.