[Measures to prevent invasion of small creatures and litter]
• Block all gaps in the piping penetration areas with putty or heat insu-
lating material (arranged in the local field) as shown in the figure
below.
(If small creatures, such as insects, or litter, enters the outdoor unit,
a short-circuit may be caused inside the electric parts box.)

6-5 Heat insulation of piping

• Make sure to insulate the field pipings (on both the liquid line and gas
line) and refrigerant branching kit.
(If they are not insulated, water leakage may be caused.)
(The maximum temperature of the piping on the gas line is about
248 °F during heating operation. Use an insulation sufficiently resis-
tant to this temperature.)
• Reinforce the refrigerant piping according to the installation environ-
ment. If it is not reinforced, condensate may form on the surface of
the insulation.
WARNING
• Make sure to insulate the field piping up to the piping connection
area inside the unit. If the piping is exposed, dew condensation and
burn by contact may be caused.
6-6 Airtight test and vacuum drying
The unit has been checked for leaks by the manufacturer.
Confirm that the valves are firmly closed before airtight test or vacuum-
drying.
To prevent entry of any impurities and insure sufficient pressure resis-
tance, always use the special tools dedicated for R410A.
Perform the following inspections securely after the piping work.
• Airtight test - Make sure to use nitrogen gas. (For the service port
position, refer to the figure in "Stop valve operation method".)
[Procedure] Pressurize the air conditioner from the liquid pipe and
gas pipe up to 450 psi (Make sure not to exceed 450 psi). When the
pressure does not drop for 24 hours, the piping work shall be
accepted.
If the pressure drops, check for leakage positions. (Confirm that
there is no leakage, then release nitrogen.)
• Vacuum drying - Use a vacuum pump which can evacuate up to
–14.6 psi or less.
[Procedure] Operate the vacuum pump for evacuation for 2 hours or
more using both liquid pipe and gas pipe until the vacuum pressure
reaches –14.6 psi or less. Leave the air conditioner at –14.6 psi or
less for 1 hour or more, and confirm that the vacuum pressure indi-
cated by the vacuum gage does not increase.
(If the vacuum pressure increases, the system may contain moisture
or have leakage.)
If there is a possibility of moisture remaining in the piping (for
example, when there is a possibility of dew condensation inside the pip-
ing because the piping work was performed in the rainy season or over
a long period of time, or when rainwater may have entered the piping
during the work)
Perform evacuation described above for 2 hours (vacuum drying), pres-
surize the air conditioner up to 7 psi (vacuum break) with nitrogen gas,
then evacuate the air conditioner using the vacuum pump for 1 hour to
achieve –14.6 psi or less (vacuum drying).
(If the vacuum pressure does not reach –14.6 psi or less even after
evacuation for 2 hours or more, repeat vacuum break and vacuum dry-
ing.) Leave the air conditioner in the vacuum status for 1 hour or more,
and confirm that the vacuum pressuree indicated by the vacuum gauge
does not increase.
10
Putty or heat
insulating material
(arranged in local field)

6-7 Additional refrigerant charge

WARNING
• To avoid injury always use protective gloves and eye protection
when charging refrigerant.
• To avoid injury do not charge with unsuitable substances. Use only
the appropriate refrigerant.
NOTE
• Refrigerant cannot be charged until field wiring has been completed.
Refrigerant may only be charged after performing the airtight test
and the vacuum drying (see above).
When charging refrigerant into the system, take care that its maxi-
mum allowable charge is never exceeded, in view of the danger of
liquid hammer.
Refrigerant containers shall be opened slowly.
To avoid compressor breakdown, do not charge the refrigerant more
than the specifed amount to raise the condensing pressure.
• This outdoor unit is factory charged with refrigerant.
• Charge the additional refrigerant calculated by the formula below.
Additional charging amount
(lb.)
Record the additional amount to the label sticked on the back of front
panel.
• Charge the refrigerant to the liquid pipe in its liquid state. Since R410A
is a mixed refrigerant, its composition changes if charged in a state of
gas and normal system operation would no longer be assured.
• Before filling, check whether the tank has a siphon attached or not.
How to fill a tank with a siphon attached.
Fill with the tank upright.
There is a siphon tube
inside, so there is no need
to turn the tank upside-down.
Other ways of filling the tank
Fill with the tank upside-down.
• Determine the amount of refrigerant to be added by referring to the
table in "6-6 Example of connection", write it down on the label
sticked on the back side of the front cover.
• After the vacuum drying is finished, charge the additional refrigerant
in its liquid state through the liquid stop valve service port.
Taking into account following instructions:
1.
Check that gas and liquid stop valves are closed.
2.
Charge the specified amount of refrigerant.
• If the outdoor unit is not in operation and the total amount cannot be
charged, follow the procedures for additional refrigerant charge
shown below.
• Make sure to use installation tools you exclusively use on R410A
installations to withstand the pressure and to prevent foreign mate-
rials from mixing into the system.
• Procedures for charging additional refrigerant.
Pressure
reducing
valve
Liquid line
R410A
Weighing
Vacuum pump
scale
Liquid piping length × 0.036
=
(ft.)×0.036
Dotted lines
represent
field piping
Outdoor unit
Gas line
Indoor units
Valve A
Stop valve service port
Charge hose

Hide quick links: