RS900 Family Installation Guide
6 Technical Specifications
6.1 Operating Environment
Parameter
Ambient Operating Temperature
Ambient Storage Temperature
Ambient Relative Humidity
Table 11 - Operating Environment
6.2 Power Supply Specifications
Power Supply Type
12 – 24 VDC
24 VDC
48 VDC
HI (125/250 VDC)
1
HI (110/230 VAC)
1
Table 12 - Power Supply Specifications
NOTES:
1.
This is the same power supply for both AC and DC.
2.
(F) Denotes fast-acting fuse, (T) denotes time-delay fuse.
3.
For continued protection against risk of fire, replace only with same type and rating of fuse.
6.3 Failsafe Relay Specifications
Parameter
Max Switching Voltage
Rated Switching Current
Table 13 - Failsafe Relay Specification
NOTES:
1.
Resistive Load.
2.
For Class-2 circuits only.
© 2008 RuggedCom Inc. All rights reserved.
Range
-40 to 85°C
-40 to 85°C
5% to 95%
Minimum
Maximum
Input
Input
10 VDC
36 VDC
18 VDC
36 VDC
36 VDC
72 VDC
88 VDC
300 VDC
85 VAC
265 VAC
30VAC, 80VDC
0.3A @ 30VAC
1A @ 30VDC, 0.3A @ 80VDC
Page 33 of 42
Comments
Ambient Temperature as measured from a 30 cm radius
surrounding the center of the enclosure.
Non-condensing
Fuse
Isolation
Rating
3.15 (T)
1.5 kV DC
3.15 (T)
1.5 kV DC
3.15 (T)
1.5 kV DC
4 kV AC
3.15 (T)
5.5 kV DC
Value
Maximum Power
Consumption
10W
Rev100