Critical Alarm Wiring; Critical Alarm Relay Connector - RuggedCom RuggedBackbone RX1510 Hardware Installation Manual

Hide thumbs Also See for RuggedBackbone RX1510:
Table of Contents

Advertisement

3. Installation
• The placement of the AC and DC power supplies is not slot-dependent. Either PM
slot can be used for AC or DC power.
• For 110/230VAC rated equipment, an appropriately rated AC circuit breaker must
be installed.
• For 125/250VDC rated equipment, a appropriately rated DC circuit breaker must be
installed.
• For maximum redundancy in a dual power supply configuration, it is recommended
to use two independent power sources.
• It is recommended to provide a separate circuit breaker for each power supply
module.
• Equipment must be installed according to applicable local wiring codes.

3.3. Critical Alarm Wiring

The Critical Alarm output relay signals critical error conditions that may occur on the
RuggedBackbone™ RX1510. The contacts are energized upon power-up of the unit and remain
energized unless a critical alarm condition is detected. Relay connections are shown in the
Alarm Relay Connector
user interface.
A common application for this output is to signal an alarm in case of a power failure.
Figure 3.15. Critical Alarm Relay Connector
RuggedCom® RuggedBackbone™
diagram. You can configure control of the relay output through the ROX™
23
RX1510 Installation Guide Rev 104
Critical

Advertisement

Table of Contents
loading

Table of Contents