Advertisement

TriMax Operation
Status Line Message
Standby
CH Demand
DHW Demand
CH / DHW Demand
DHW Priority
Priority Timeout
External Demand
Slave Operation
Manual Operation
CH Burner Delay
DHW Burner Delay
CH Setpoint Reached
DHW Setpoint Reached
CH Post Pump
DHW Post Pump
Freeze Protection
Boiler Protection
Lockout Description

Status Line Messages

Indicates that the Prestige is ready to respond when a demand is received.
A central heating call has been received.
A domestic hot water call has been received.
Central heating and domestic hot water calls are being received simultaneously.
Both calls are being satisfied simultaneously because domestic hot water priority
has been disabled.
Central heating and domestic hot water calls are being received simultaneously.
Domestic hot water call is being satisfied first because it has priority over central
heating calls.
Central heating and domestic hot water calls are being received simultaneously.
The domestic hot water priority time limit has been exceeded. Priority will now
switch back and forth between central heating and domestic hot water calls until
one call is satisfied.
An external modulation call has been received.
The Prestige is a slave in a cascade system.
The burner or circulators have manually been enabled in the Installer Menu.
The burner will not fire until the call blocking time has elapsed.
The burner will not fire until the call blocking time has elapsed.
The burner is not fired because the supply/system water temperature exceeds
the setpoint. The central heating circulator continues to operate and the burner
will fire again once the supply/system water temperature drops below the set-
point.
The burner is not fired because the supply/system water temperature exceeds
the setpoint. The domestic circulator continues to operate and the burner will fire
again once the supply/system water temperature drops below the setpoint.
The central heating circulator is running to remove heat from the Prestige at the
completion of a call.
The domestic hot water circulator is running to remove heat from the Prestige at
the completion of a call.
The burner is fired because the freeze protection feature has been activated.
Freeze protection will end once the supply/system water temperature is raised to
60ºF [16ºC].
The burner firing rate is being reduced because of an excessive difference
between the boiler supply and return temperatures. The firing rate will begin
increasing once the temperature difference is less than 45ºF [25ºC].
The lockout which currently has the Prestige shut down is displayed.