PRODUCT DESIGN
HKR ELECTRICAL DATA
Model and Heat Kit Usage
GPC1336M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
HKR15A,CA
GPC1348M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
HKR15A,CA
HKR20A,CA
GPC1360M41*
HKR05A,CA
HKR08A,CA
HKR10A,CA
HKR15A,CA
HKR20A,CA
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
Supply Votage
Correction Factor
Multiply rated kW by correction factor to get actual kW
All wires and overcurrent protection devices are sized for use with electric heaters only and without
WARNING
WARNING
refrigeration.
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
6
Circuit #1
Maximum
Minimum Circuit
Overcurrent
Ampacity
Protection (amps)
at 208 / 240V
at 208 / 240V
24 / 27
30 / 30
34 / 39
40 / 40
45 / 52
60 / 60
45 / 52
60 / 60
25 / 28
30 / 30
34 / 40
40 / 40
46 / 53
60 / 60
46 / 52
60 / 60
46 / 52
60 / 60
25 / 28
30 / 30
34 / 40
40 / 40
46 / 53
60 / 60
46 / 52
60 / 60
46 / 52
60 / 60
Heating kW Correction Factor
240
230
1.0
0.93
If heaters are not installed with above wire size, overheating and fire could occur. See
GPC13[36-60]M41*
Circuit #2
Maximum
Minimum Circuit
Overcurrent
Ampacity
Protection (amps)
at 208 / 240V
at 208 / 240V
----
----
----
----
----
----
22 / 25
30 / 30
----
----
----
----
----
----
22 / 25
30 / 30
43 / 49
60 / 60
----
----
----
----
----
----
22 / 25
30 / 30
43 / 49
60 / 60
220
210
0.85
0.78
Actual
kW & BTU
at 240V
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
14.25 / 48,600
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
14.25 / 48,600
19.50 / 66,500
4.75 / 16,200
7.00 / 23,800
9.50 / 32,400
14.25 / 48,600
19.50 / 66,500
208
0.76