F) Temperature Display Scale (F5); G) Alarm History (F6) - Hoshizaki HUR40A(-D) Service Manual

Commercial refrigerators & freezers undercounter & worktop series
Hide thumbs Also See for HUR40A(-D):
Table of Contents

Advertisement

4) Press the
unmarked, blank button to save the setting.
5) Press the MANUAL DEFROST button to return to the menu screen. Press and hold
both the
button and the
mode and return to the temperature display.
6) If a jumper was present between connector K151 pins 7 and 8, reconnect it after all
setting and diagnostic work is complete.

f) Temperature Display Scale (F5)

For information about switching the display between °F and °C, see "D.2.a) Switching
the Display Between Fahrenheit and Celsius (F5)."

g) Alarm History (F6)

To view the alarm history, follow the steps below.
1) Make sure the jumper is removed between connector K151 pins 7 and 8 on the control
board. Otherwise you will not be able to access this setting. For details, see "D.1.
Gaining Access to Settings and Diagnostics."
2) Press and hold both the
"F0" should appear in the display window. Press the MANUAL DEFROST button until
"F6" appears in the display window.
3) Press the
unmarked, blank button to display the alarm history. The alarms will be
displayed in reverse chronological order (newest to oldest - up to 8 alarms). When "--"
is displayed, you have reached the end of the alarm history and the display will begin
again.
Note: The alarms are as follows:
Alarm Code Description
4) To reset the alarm history, press and hold both the
MANUAL DEFROST button for 5 seconds.
5) Press the MANUAL DEFROST button to return to the menu screen. Press and hold
both the
button and the
mode and return to the temperature display.
6) If a jumper was present between connector K151 pins 7 and 8, reconnect it after all
setting and diagnostic work is complete.
unmarked, blank button for 5 seconds to exit the setting
button and the
E1
High Temperature Alarm
E2
Low Temperature Alarm
E3
Defrost Alarm
E4
High Pressure Alarm
E7
Clogged Filter Alarm
E8
Defrost Temperature Sensor Malfunction Alarm
E9
Clogged Filter Sensor Malfunction Alarm
EA
EEPROM Write Error Alarm
ED
EEPROM Verification or Read Error Alarm
unmarked, blank button for 5 seconds to exit the setting
unmarked, blank button for 5 seconds.
unmarked, blank button and the
30