Connect water piping
14
General piping information:
ASME
or
Canadian
requirements
If installation
is to comply with ASME or Canadian
requirements, an additional high
temperature
limit is
needed.
Install control in
supply
piping
between boiler
and
isolation
valve.
Set control
to
a
minimum
of 20
op
above set point of
the
boiler
limit
temperature
sensor.
Maximum allowable set
point is
220 °F. Wire control
as
shown
on wiring diagram
(page
20 &
21).
Low
water cutoff
devices
The Hydrostat
3250 control has an
integrated LWCO
device.
The probe for the control is
inserted
into the
well located on
the top
off the
boiler.
Ensure the
probe
is
fully inserted into the
well.
Backflow prevention
Use backtlow check valve
in
cold water supply as
re-
quired
by local
codes.
Install piping:
Pipe
sizing
See
Table
3 for pipe sizing for near-boiler piping and
single-zone
piping.
Near-boiler piping
(with diaphragm expansion tank)
See
Figure
6, page
15.
Near-boiler piping
(with closed expansion
tank)
See
Figure
7,
page
15.
Multiple-zone piping
See page
16.
Low-temperature
system
piping
See page
17.
Chiller
system
piping
See page
18.
For multiple-boiler piping
Refer
to Weil-McLain's "Primary/Secondary
Piping
Guide."
Relief valve
Install relief
valve vertically
in
elbow supplied. See
Figure 6 or 7 for
location.
See WARNING at
right.
Also
refer
to tag attached to
relief
valve for
manufac-
turer's
instructions.
Table
3
Water
piping sizing
Piping to
Piping from
Model
system
system
(inches)
(inches)
U0-3
1%
1%
U0-4
1%
1%
U0-5
1112
1112
Note: sizing based on 20°F temperature rise
through
boiler.
IAWARNINGI
Relief valve discharge piping:
To avoid water
damage or
scalding
due to relief
valve operation:
Discharge line must
be connected to
relief
valve outlet
and
run
to
a safe place
of
disposal.
Terminate the
discharge
line to
eliminate
possibility
of severe
burns
should
the
valve
discharge.
Discharge line must be
as short as
pos-
sible
and be
the same size
as the
valve
discharge connection throughout its
entire
length.
Discharge line must
pitch downward
from
the valve
and terminate at least
6"
above the floor drain where any
discharge
will
be clearly
visible.
• The
discharge
line
shall terminate
plain,
not threaded,
with
a material
serviceable for
temperatures of 375
op
or greater.
Do not
pipe
the discharge to
any place
where
freezing
could
occur.
• No
shutoff valve shall be
installed be-
tween
the relief
valve
and
boiler,
or in
the discharge line. Do not plug or
place
any
obstruction
in the discharge line.
Failure to
comply with
the
above
guide-
lines could result in
failure of
the relief
valve
to
operate,
resulting in
possibil-
ity of
severe
personal injury, death
or
substantial
property
damage.
• Test the
operation of
the
valve after
filling and pressurizing
system
by
lifting the
lever.
Make sure
the
valve
discharges
freely.
If the
valve
fails to
operate correctly,
replace it with a new
relief
valve.
Part number
550-1
41 -987/0912