Thermostat Installer Setup Options - Honeywell Chronotherm IV T8601D Installation Instructions Manual

Deluxe programmable thermostat
Hide thumbs Also See for Chronotherm IV T8601D:
Table of Contents

Advertisement

T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
Installer Setup
Number
(Press Time !
Select
key to change)
Not used
a
Fan operation
Not used
Heating cycle
rate
Not used
5 thru 11
System setting
adjustment
Adaptive
Intelligent
Recovery™
control
Degree
temperature
display
Not used
Clock format
Not used
17 and 18
Extended fan
operation in
a
heating
Extended fan
operation in
a
cooling
Not used
21 thru 23
Outdoor
temperature
display (select
models)
Not used
25 thru 29
Deadband
Not used
31 and 32
Minimum off
time for the
compressor
69-1410—2
Table 3. Thermostat Installer Setup Options.
Factory-Setting
Display
1
2
0
Conventional application
where equipment control
fan operation in heat mode
3
4
6
6—6 cph used for
12
1
Manual changeover.
13
0
Adaptive Intelligent
Recovery™ control is
activated (system starts
early so setpoint is reached
by start of program period)
14
0
Temperature is displayed
in °F
15
16
0
12-hour clock format
19
0
No extended fan operation
after the call for heat ends
20
0
No extended fan operation
after the call for cool ends
24
0
No outdoor temperature is
displayed
30
3
Heating and cooling
setpoints can be set no
closer than 3°F (1.5°C)
33
5
5 minute minimum off- time
for the compressor.
Description
conventional heat.
6
Other Choices
(Press ! or " key to change)
Display
Description
1
Heat pump or electric
heat applications where
thermostat controls fan
operation in heat mode
1, 3 or 9 1—1 cph used for radiant
floor heat, gravity
system
3—3 cph used for hot
water systems or high
efficiency furnaces
9—9 cph used for electric
heat systems
0 or 2
0—Auto changeover
2—Auto only
1
Conventional recovery
(system starts recovery at
programmed time)
1
Temperature is displayed
in °C
1
24-hour clock format
1
Fan operation is
extended 90 seconds
after the call for heat
ends
1
Fan operation is
extended 90 seconds
after the call for cool ends
1
Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Sensor to operate
4 thru 10 Heating and cooling
setpoints can be set no
closer that chosen value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
0 thru 4 Minimum number of
minutes (0 thru 5) the
compressor is off
between calls for the
compressor
Actual
Setting