Set Clock - Honeywell 191108AC Installation Instructions Manual

Heating, cooling and heating/cooling thermostat, wallplate, and subbase
Hide thumbs Also See for 191108AC:
Table of Contents

Advertisement

Fig. 8—Set clock.
M1813A

SET CLOCK

Adjust the clock by moving the minute hand in a clock-
wise
direction. Do not reverse the minute hand.
When time is correctly set, the time indicator arrow (tri-
angle shape) points to the correct time and the corresponding
daytime (light) or nighttime (dark) portion of the program dial.
Fig. 9—Adjust heat anticipator.
ANTICIPATOR
SCALEPLATE
ANTICIPATOR
SETTING LEVER
Fig. 10—Current rating of primary control.
SHOWS
VOLTAGE
RATING
V8043E 1004 4
24V 50/60CY
SHOWS
.32 AMP @ 60CY
ANTICIPATOR
SETTING
ZONE VALVE
PROGRAM DIAL
MINUTE
HAND
TIME
INDICATOR
ARROW
M7317
SHOWS
VOLTAGE
RATING
24 Vac 50/60 Hz
0.4 AMP
FROM MAIN
FUEL SUPPLY
TYPICAL GAS VALVE
SET HEAT ANTICIPATOR
Adjust the heat anticipator lever to match the current
rating of the primary control for the proper cycle rate (Fig. 9).
Adjustable anticipation must be set for total current of
heat and fan control.
The current rating is usually stamped on the control or
valve (Fig. 10), or a setting may be given in the device
instructions.
If no current rating or heat anticipator setting is given,
measure the current with an ammeter. Proceed with the fol-
lowing steps.
Remove the thermostat from the wallplate or subbase.
Connect an ac ammeter of appropriate range (about 0A to
2A) between the R and W terminals on the wallplate or sub-
base except for electric heat and heat pump systems.
Let the system operate for one minute.
Adjust the heat anticipator lever to match the number that
reads on the ammeter.
ATTACH THERMOSTAT COVER
Make sure the packing inserts in the thermostat base are
removed.
Place the two tabs on the upper edge of the cover into the
mounting slots in the thermostat base (Fig. 11).
Swing the cover downward until it catches at the bottom
of the base.
Fig. 11—Attach cover.
M1519
TO
BURNER
SHOWS
ANTICIPATOR
SETTING
5
OIL BURNER CONTROL
SHOWS
SHOWS LOW
CURRENT
VOLTAGE
DRAW
T
T
F
F
M6116A
69-0638—1