Set Clock; Typical Gas Valve - Honeywell Q682B Manual

Hide thumbs Also See for Q682B:
Table of Contents

Advertisement

Fig. 7—Insert clock batteries.
BATTERY LOCATION FOR
(2) AAA BATTERIES;
INSTALL WITH POSITIVE
ENDS UP

SET CLOCK

Adjust the clock by moving the minute hand in a clock-
wise
direction. Do NOT reverse the minute hand.
When time is correctly set, the time indicator arrow (Fig. 8)
must point to the correct time and the corresponding daytime
(light) or nighttime (dark) portion of the program dial.
SET HEAT ANTICIPATOR
Adjust the heat anticipator lever to match the current
rating of the primary control for the proper cycle rate (Fig. 9).
Adjustable anticipation must be set for total current of heat
and fan control.
The current rating is usually stamped on the control or
valve (Fig. 10), or a setting may be given in the device
instructions.
If no current rating or heat anticipator setting is given,
measure the current with an ammeter. Proceed with the
following steps.
Remove thermostat from wallplate or subbase. Connect
an ac ammeter of appropriate range (about 0A to 2A) be-
tween the R and W terminals on the wallplate or subbase
except in electric heat and heat pump systems.
Fig. 10—Current rating of primary control.
SHOWS
VOLTAGE
RATING
V8043E 1004 4
24V 50/60CY
SHOWS
.32 AMP @ 60CY
ANTICIPATOR
SETTING
ZONE VALVE
M7188
SHOWS
VOLTAGE
RATING
24 Vac 50/60 Hz
0.4 AMP
FROM MAIN
FUEL SUPPLY

TYPICAL GAS VALVE

5
Fig. 8—Set clock.
Let the system operate for one minute.
Adjust the heat anticipator lever to match the number that
reads on the ammeter.
Fig. 9—Adjust heat anticipator.
ANTICIPATOR
SCALEPLATE
ANTICIPATOR
SETTING LEVER
TO
BURNER
SHOWS
ANTICIPATOR
SETTING
MINUTE
HAND
TIME
INDICATOR
ARROW
M8561
M7317
OIL BURNER CONTROL
SHOWS
SHOWS LOW
CURRENT
VOLTAGE
DRAW
T
T
F
F
M6116A
69-0431—2

Advertisement

Table of Contents
loading

This manual is also suitable for:

T8090a

Table of Contents