Refrigeration Cycle Diagram - LG LT-E1820CL Manual

Ceiling cassette air conditioner exploded view
Hide thumbs Also See for LT-E1820CL:
Table of Contents

Advertisement

Refrigeration Cycle Diagram

• HEAT PUMP
INDOOR UNIT
H/EX
CAPI C1
CAPI C2
(
Pipe Size
Capacity
GAS
LIQUID
18K
5/8"
1/4"
24K
5/8"
1/4"
• Rated performance for refrigerant line length of: 7.5m
• If 18K Capacity is installed at a distance of 15m, 187.5g of refrigerant
should be added ....................................................(15-7.5)x25g
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Liquid Side
Gas Side
Liquid Side
Gas Side
Length (m)
Elevation (m)
Max.
Max.
Rated
Rated
7.5
50
5
30
7.5
50
5
30
OUTDOOR UNIT
ACCUM.
VALVE REVERSING
Heating
COMPRESSOR
* Additional
refrigerant
(g/m)
25
30
- 12 -
CAPI A
H/EX
Cooring
CAPI B
LGE Internal Use Only