This table is created using the maximum capacity.
INDOOR UNIT 18000BTU (AOU36R)
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
COOLING
Indoor unit is upper
than outdoor unit
Height difference H
Indoor unit is under
than outdoor unit
HEATING
Indoor unit is upper
than outdoor unit
Height difference H
Indoor unit is under
than outdoor unit
Indoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
15m 49ft.
1
10m 33ft.
7.5m 25ft.
0.994 0.992 0.990 0.984 0.977 0.970
5m
16ft.
0m
0ft. 1.002 1.000 0.998 0.992 0.985 0.978
1.002 1.000 0.998 0.992 0.985 0.978
-5m -16ft.
2
-7.5m -25ft.
-10m -33ft.
-15m -49ft.
15m 49ft.
1
10m 33ft.
7.5m 25ft.
5m
16ft.
1.000 1.000 0.990 0.950 0.917 0.901
0m
0ft. 1.000 1.000 0.990 0.950 0.917 0.901
-5m -16ft.
0.995 0.995 0.986 0.945 0.912 0.896
2
-7.5m -25ft.
-10m -33ft.
-15m -49ft.
Height difference H
H
Outdoor unit
- (02 - 08) -
Pipe length
5m
7.5m
10m
15m
20m
16ft.
25ft.
33ft.
49ft.
66ft.
-
-
-
0.968 0.961 0.954
-
-
0.982 0.976 0.969 0.962
-
0.988 0.986 0.980 0.973 0.966
-
1.000 0.998 0.992 0.985 0.978
-
-
0.998 0.992 0.985 0.978
-
-
-
0.992 0.985 0.978
Pipe length
5m
7.5m
10m
15m
20m
16ft.
25ft.
33ft.
49ft.
66ft.
-
-
-
0.950 0.917 0.901
-
-
0.990 0.950 0.917 0.901
1.000 0.990 0.950 0.917 0.901
-
0.993 0.983 0.943 0.910 0.894
-
-
-
0.981 0.940 0.908 0.892
0.935 0.903 0.887
-
-
-
Outdoor unit
H
Connection pipe
2
Indoor unit is under than outdoor unit.
25m
82ft.
25m
82ft.
Indoor unit