This table is created using the maximum capacity.
INDOOR UNIT 12000BTU (AOU36R)
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
COOLING
Indoor unit is upper
than outdoor unit
Height difference H
Indoor unit is under
than outdoor unit
HEATING
Indoor unit is upper
than outdoor unit
Height difference H
Indoor unit is under
than outdoor unit
Indoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
15m 49ft.
1
10m 33ft.
7.5m 25ft.
0.995 0.992 0.987 0.975 0.958 0.939
5m
16ft.
0m
0ft.
1.003 1.000 0.995 0.982 0.966 0.947
-5m -16ft.
1.003 1.000 0.995 0.982 0.966 0.947
2
-7.5m -25ft.
-10m -33ft.
-15m -49ft.
15m 49ft.
1
10m 33ft.
7.5m 25ft.
5m
16ft.
1.003 1.000 0.994 0.974 0.926 0.901
0m
0ft.
1.003 1.000 0.994 0.974 0.926 0.901
-5m -16ft.
0.998 0.995 0.989 0.969 0.921 0.897
2
-7.5m -25ft.
-10m -33ft.
-15m -49ft.
Height difference H
H
Outdoor unit
- (02 - 07) -
Pipe length
5m
7.5m
10m
15m
20m
16ft.
25ft.
33ft.
49ft.
66ft.
-
-
-
0.959 0.943 0.924
-
-
0.979 0.967 0.950 0.931
-
0.988 0.983 0.971 0.954 0.935
-
1.000 0.995 0.982 0.966 0.947
-
-
0.995 0.982 0.966 0.947
-
-
-
0.982 0.966 0.947
Pipe length
5m
7.5m
10m
15m
20m
16ft.
25ft.
33ft.
49ft.
66ft.
-
-
-
0.974 0.926 0.901
-
-
0.994 0.974 0.926 0.901
1.000 0.994 0.974 0.926 0.901
-
-
0.993 0.987 0.966 0.919 0.894
0.984 0.964 0.917 0.892
-
-
0.959 0.912 0.888
-
-
-
Outdoor unit
H
Connection pipe
2
Indoor unit is under than outdoor unit.
25m
82ft.
25m
82ft.
Indoor unit