Resetting Diagnostics; Diagnostics - Trane UniTrane Installation Operation & Maintenance

Fan-coil room conditioners force flo cabinet heaters low vertical fan-coils
Table of Contents

Advertisement

Table 43. TUC Controller Diagnostics
Diagnostic
Latching?
Dirty filter
Yes
Condensate
Yes
overflow
Supply fan
Yes
failure (if
configured as
alarm = yes)
Supply fan
Yes
failure (if
configured as
alarm = no)
Low coil
Yes
entering air
temp
Notes:
1.
Use a normally open hot water valve with the low coil entering air temperature sensor.
2.
Use a normally closed chilled water valve with the condensate overflow sensor.
Resetting

Diagnostics

Using the Zone Sensor
Using
Everyware
Software
UNT-IOM-6
Diagnostics
Fan
Valves
No Action
No Action
Off
Closed
Off
Closed
No Action
No Action
Off
Open
There are five ways in which diagnostics are reset:
1. Using the zone sensor
2. Using Everyware™, Trane's TUC service tool
3. By cycling power to the TUC
4. Through Tracer 100i ™ or 100L ™
5. Through Tracer Summit
Using the zone sensor's fan mode switch to reset diagnostics, slide
the fan mode switch to the off position. Then return the switch back to
any position except off.
Connect to the communications terminal with a laptop computer
loaded with Everyware ™ software. Log on and reset the diagnostics
from the diagnostic page of the TUC configuration screens. To view
the diagnostics prior to resetting, press the ENTER key while in the
status section of the service summary screens.
Terminal Unit
Control (TUC)
Elect. Heat
Damper
No Action
No Action
Off
Closed
Off
Closed
No Action
No Action
Off
Closed
®
107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents