Function

2. Special Control

2.1 Oil return control

2.1.1 Oil return control on cooling mode
Oil return operation recovers oil amount in compressor by collecting oil accumulated in pipe.
Each cycle component operates as following table during oil return operation.

Outdoor Unit

Component
Inverter compressor
Fan
Main EEV
Subcooling EEV
4way valve
Hot gas bypass valve
Indoor Unit
Component
Fan
Thermo on unit EEV
Thermo off unit EEV
Oil return signal
I Oil return operation time : 6 min. for running step
I Starting condition:every 6 hours operate
I Oil return process ends if compressor protection control starts
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Starting
30Hz
Setting Value
Normal control
Normal control
Max. pulse
Min. pulse
OFF
Normal control
Normal control
Starting
Normal control
Normal control
Normal control
Min. pulse
OFF
- 18 -
Running
Normal control
Max. pulse
Max. pulse
Min. pulse
100 pulse
OFF
Normal control
Running
Normal control
1200 pulse
Normal control
1200 pulse
Min. pulse
ON
LGE Internal Use Only
Ending
40Hz
OFF
Ending
OFF