Cooling - Trane 4YCY4060A Product Data

Single packaged convertible gas/electric 14 seer 2 - 5 ton, 40 - 120 kbtu r-410a
Table of Contents

Advertisement

4YCY4030A1 AT 1000 NOM CFM
OD
ID
TOT
SENS CAP AT ENTERING DB TEMP
AMB
WB
CAP
72
59
29.8
24.1
63
31.0
19.7
85
67
33.4
15.8
71
36.1
11.8
59
27.3
23.0
63
28.5
18.7
95
67
30.7
14.7
71
33.1
10.7
59
24.8
21.9
63
25.9
17.6
105
67
27.9
13.7
71
30.1
9.7
59
22.4
20.8
63
23.3
16.6
115
67
25.1
12.7
71
27.1
8.7
4YCY4024A1 AT 800 NOM CFM
OD
ID
TOT
SENS CAP AT ENTERING DB TEMP
AMB
WB
CAP
72
59
22.9
19.1
63
23.9
15.6
85
67
25.8
12.3
71
27.8
9.1
59
20.9
18.2
63
21.8
14.7
95
67
23.5
11.5
71
25.3
8.3
59
18.8
17.3
63
19.6
13.8
105
67
21.1
10.6
71
22.8
7.4
59
16.7
16.4
63
17.5
13.0
115
67
18.8
9.8
71
20.3
6.6
4YCY4036A1/3 AT 1200 NOM CFM
OD
ID
TOT
SENS CAP AT ENTERING DB TEMP
AMB
WB
CAP
72
59
34.5
28.8
63
36.0
23.4
85
67
38.8
18.5
71
41.9
13.5
59
32.0
27.6
63
33.4
22.3
95
67
35.9
17.4
71
38.8
12.4
59
29.5
26.5
63
30.7
21.2
105
67
33.1
16.3
71
35.7
11.4
59
26.9
25.4
63
28.1
20.2
115
67
30.2
15.3
71
32.7
10.4
Performance Data Cooling
(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
TOTAL
75
78
80
KW
26.9
29.2
28.9
2.3
22.6
25.5
27.4
2.3
18.6
21.5
23.4
2.3
14.6
17.5
19.4
2.3
25.8
27.3
27.3
2.5
21.5
24.4
26.3
2.5
17.6
20.4
22.3
2.5
13.6
16.5
18.4
2.5
24.7
24.8
24.8
2.7
20.5
23.3
25.2
2.7
16.5
19.4
21.3
2.7
12.6
15.4
17.4
2.7
22.4
22.4
22.4
2.9
19.5
22.3
23.3
2.9
15.5
18.4
20.3
2.9
11.6
14.4
16.4
2.9
(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
TOTAL
75
78
80
KW
21.4
22.9
22.9
1.8
17.9
20.2
21.8
1.8
14.7
17.0
18.6
1.9
11.5
13.8
15.3
1.9
20.5
20.9
20.9
2.0
17.0
19.3
20.9
2.0
13.8
16.1
17.7
2.0
10.6
12.9
14.5
2.0
18.8
18.8
18.8
2.1
16.1
18.5
19.6
2.1
12.9
15.3
16.8
2.2
9.7
12.1
13.6
2.2
16.7
16.7
16.7
2.3
15.3
17.5
17.5
2.3
12.1
14.4
16.0
2.3
8.9
11.2
12.8
2.3
(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
TOTAL
75
78
80
KW
32.4
34.5
34.5
2.7
27.0
30.5
32.9
2.7
22.0
25.6
27.9
2.8
17.1
20.6
23.0
2.8
31.2
32.0
32.0
3.0
25.9
29.4
31.8
3.1
20.9
24.5
26.9
3.1
16.0
19.6
21.9
3.1
29.5
29.5
29.5
3.3
24.8
28.4
30.7
3.4
19.9
23.4
25.8
3.4
15.0
18.5
20.9
3.4
26.9
26.9
26.9
3.6
23.7
27.3
28.1
3.7
18.8
22.4
24.8
3.7
13.9
17.5
19.9
3.7
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW
RATE, CFM
LOW
875
HIGH
1125
ARI RATING FOR COOLING
CFM
CAPACITY (A) TEST
890
30000
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW
RATE, CFM
LOW
700
HIGH
900
ARI RATING FOR COOLING
CFM
CAPACITY (A) TEST
790
23400
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW
RATE, CFM
LOW
1050
HIGH
1350
ARI RATING FOR COOLING
CFM
CAPACITY (A) TEST
1210
36000
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
9
CAPACITY
TOTAL POWER
MULTIPLIER
MULTIPLIER
0.97
0.98
1.03
1.02
SEER
EER
14.00
12.00
CAPACITY
TOTAL POWER
MULTIPLIER
MULTIPLIER
0.97
0.98
1.03
1.02
SEER
EER
14.00
11.60
CAPACITY
TOTAL POWER
MULTIPLIER
MULTIPLIER
0.97
0.98
1.03
1.02
SEER
EER
14.20
11.60