Hydronic piping
Figure 3-3 Pressure Drop vs. Flow
25
20
15
10
5
0
3
Table 3A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
Model
GPM
FT/HD
151
14
211
20
286
27
These pumps are only slightly above 20° rise flows, but are the closest available. To reach a 20° rise or less, an
*NOTICE
upsized pump will be required.
Model
GPM
FT/HD
151
11
211
16
286
21
Model
GPM
FT/HD
151
8
211
11
286
15
Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude
NOTICE
models.
Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude
NOTICE
models.
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.
NOTICE
(continued)
Pressure Drop vs. Flow (Includes Secondary Piping)
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Flow Rate (GPM)
20°F Temperature Rise Applications
Minimum Pipe
Size
20
1"
29
1"
15
1-1/4"
25°F Temperature Rise Applications
Minimum Pipe
Size
13
1"
19
1"
12
1-1/4"
35°F Temperature Rise Applications
Minimum Pipe
Size
10
1"
9
1"
7
1-1/4"
Outdoor Knight Boiler Installation & Operation Manual
Grundfos
TACO
UPS26-99F
0011
UPS32-160
1400-50
UPS32-80
1400-20
Grundfos
TACO
UPS26-99F
0014
UPS26-99F
0013
UPS26-99F
0011
Grundfos
TACO
UPS15-58FC
008/0010
UPS15-58FC
0010
UP26-64F
008/0010
151
211
286
Pump
B & G
Armstrong
NRF-36
PL-55
PL-36
Pump
B & G
Armstrong
NRF-36
NRF-36
NRF-36
Pump
B & G
Armstrong
NRF-36
NRF-36
NRF-36
E7
E9*
E11
E7
E7
E7
Astro-30
Astro-50
E7
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents