Installation
STEADY 'LED' FLASH
ENERGIZED
NO
ADJUST THERMOSTAT SET
TEMPERATURE HIGHER THAN
ROOM TEMPERATURE
ENERGIZED
CHECK FOR LOOSE OR BROKEN
CHECK VOLTS ACROSS 'PUMP'
CONNECTIONS ON PCB
VAC = 115V +/-
PROBLEM(S) WITH 24V TO PCB
- GO TO 24V
TROUBLESHOOTING CHART
RECONNECT WIRES AND
CONFIRM THAT WIRING IS AS
PER WIRING DIAGRAMS
CONTACT TECH.
SUPPORT
Circulating Pump 115V Troubleshooting - Flow Sensor (FS) Configuration
Figure 22:
22
WITH DOOR SWITCH CLOSED
(SET SYSTEM IN HEATING MODE
YES
YES
PUMP
COMPONENT AND RE-CHECK
PUMP
YES
NO
WIRES
YES
CONNECT PUMP DIRECTLY TO
NO
COMPONENT AND RE-CHECK
YES
NO
Rinnai Corporation Hydronic Furnace (37AHB) Manual
START
-CALL FOR HEAT)
YES
IS 'LED' ON
NO
PUMP AMP
DRAW NORMAL
NO
CHECK CAPACITOR; IF
DEFECTIVE, REPLACE
AMP DRAW
REPLACE PUMP MOTOR AND
RETURN TO START
YES
PUMP MOTOR
ENERGIZED
115 VAC POWER SUPPLY
CHECK CAPACITOR; IF
DEFECTIVE REPLACE
AMP DRAW
NO
PUMP AMP
DRAW NORMAL
RETURN TO START
SYSTEM
WORKING
YES
FINISH
RAPID 'LED' FLASH
GO TO RFH START-UP &
'LED' TROUBLESHOOTING
YES
PUMP AMP
DRAW NORMAL
NO
(1) RECTIFY WIRING PROBLEM(S)
NO
(2) CHECK MOTOR AND
CAPACITOR; IF DEFECTIVE,
REPLACE FAULTY COMPONENT(S)
RETURN TO START
NO
PUMP AMP
DRAW NORMAL
CHECK PUMP
YES
MOTOR; IF
DEFECTIVE
REPLACE
COMPONENT
AND RE-CHECK
AMP DRAW
YES
SYSTEM
WORKING
NO
YES