Download Print this page

Installation - Honeywell T4031A Product Data

Refrigeration temperature controllers

Advertisement

Electrical Ratings:
120 Vac
Normally
Closed
Full Load
8
Amp
Locked Rotor
48
Amp
a
Makes on temperature rise.
Pilot Duty:
125 VA
Dimensions:
See Fig. 1
2 (51)
15/16
(24)
17/32
(13)
4-3/16
(107)
7/32
(6)
29/32
(23)
1-3/16
3/8
(9)
(30)
Fig. 1. Dimensions of T4031, T6031 in in. (mm).
Underwriters Laboratories Inc.:
Listed
Maximum Ambient Operating Temperature:
125°F (52°C)
Accessories:
112622AA Immersion Well—short-necked, 1/2 in. NPT,
copper
7617ABY Compression Fitting—50 psi water, 15 psi air
107324A Bulb Holder—for duct installation
105900 T-strap—for strapping bulb to pipe
T4031A,B,P; T6031A,B REFRIGERATION TEMPERATURE CONTROLLERS
240 Vac
Normally
Normally
Normally
a
Open
Closed
Open
16
5.1
80
30.6
KNOCKOUT FOR 1/2 IN. (13 MM)
CONDUIT (2)
2-1/4 (57)
2-1/8 (54)
5-5/8
(136)
7/32 (6)
DIA. (3)
3/8 (10)
DIA. (3)
M4496
7617ABZ Bag Assembly—for mounting controller to fan coil
units
801534 Calibration Wrench
7640HY Standoff Bracket Bag Assembly—to mount
a
controller to an insulated duct
130883 Universal Mounting Bracket
8
194899 Tamper-resisting Insert Button
Celsius Scaleplates:
194486 D: -15°C to +35°C replaces (0°F to 100°F)
40
scaleplate
194486H: 15°C to 75°C replaces (55°F to 175°F)
194486F: 75°C to 125°C replaces (160°F to 260°F)

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation
as provided in these instructions.
CAUTION
• Disconnect power supply before installation to prevent
electrical shock and equipment damage.
• Do not damage or change shape of capsule. De-
formed capsule will cause calibration offset.
Mounting
Install controller in any convenient location. Make sure that the
sensing bulb reaches the system to be controlled. The ambient
temperature must not exceed 125°F (52°C) in the area where
the controller is installed.
Install the sensing element where it can sense the average
temperature. Avoid sharp bends or kinks in the capillary tubing
that can affect the accuracy of the controller. Carefully coil the
excess capillary tubing and leave it directly beneath the
controller.
The 130883 Mounting Plate furnished with TRADELINE®
models allows the control to be mounted in existing mounting
holes.
Duct Installation
Position the sensing bulb in the duct to sense the average air
temperature. Avoid mounting the bulb close to hot pipes,
cooling coils, etc.
The 107324A Bulb Holder is available for suspending the bulb
in a duct. See Fig. 2.
3
60-2177—3