Mitsubishi Electric Mr.SLIM PKA-A12GA Service Manual page 37

Split-type, heat pump air conditioners split-type, air conditioners
Table of Contents

Advertisement

(2) Setting method of each function by wired remote controller
1. Stop running the air-conditioner( ).
2. Press the
TEST
button ( ) for 3 seconds so that [Maintenance mode] appears on the screen (at
After a while, [00] appears in the refrigerant address number display area.(at
3. Press the
CHECK
button ( ) for 3 seconds to switch to [Maintenance monitor].
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
(i.e., while"----" is blinking) since no buttons are operative.
[----] appears on the screen (at
(The display (at
) now allows you to set a request code No.)
4. Press the [TEMP (
[Screen ]
5. Press the [CLOCK (
"331~335")
6. Press the
button ( ) to perform function setting.
FILTER
If the above operations are set correctly, request code number will appear in data display area.(at
[Example) When the request code number is "311", [311] appears on the screen.(at
[Refererence]
You can check the request code number of current setting by setting the request code number ("310", "320" or "330") and
press the
FILTER
button.( )
[Example) When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.(at
7. To return to normal mode, press the
11-2. BACK-UP HEATING FUNCTION(CN24)
11-2-1. Operation
Outline of functions
The back-up heater signal is sent out according to the temperature
difference between indoor room temperature and set temperature.
This function is available only in heating operation.
11-2-2. How to connect
When connecting to the connector CN24 of the indoor unit, use
PAC-SE56RA-E(optional parts).
) when [Maintenance monitor] is activated.
and
)] buttons ( ) to select the desired refrigerant address.
and
)] buttons ( ) to set the desired request code No.("311~318", "321~324",
button ( ).
ON/OFF
37
B: Refrigerant address
C: Data display area
D: Request code display area
)
)]
Temperature difference
(Z=Set temp. - Room temp.)
1
Z
0 (°F)
2
0 < Z < 2.5 (4.5°F)
2.5 (4.5°F)
3
Z
0
).
)
)]
Back-up heater
signal output
OFF
Keeping condition
Z
ON
ON
OFF
2.5°C(4.5°F)