Gas Supply Line
Provide a gas supply line of sA" (1.9 cm) rigid pipe to the
range location. A smaller size pipe on longer runs may result
in insufficient gas supply. Pipe-joint compounds
that resist
the action of LP gas must be used. Do not use TEFLON ®t
tape. With LP gas, piping or tubing size can be r/2" (1.3 cm)
minimum. Usually, LP gas suppliers determine the size and
materials used in the system.
Flexible metal appliance connector:
If local codes permit, a new CSA design-certified,
4 to 5 ft (122 to 152.4 cm) long, r/2" (1.3 cm) or
3A" (1.9 cm) I.D., flexible metal appliance connector may
be used for connecting range to the gas supply line.
A r/2" (1.3 cm) male pipe thread is needed for connection
to the female pipe threads of the inlet to the appliance
pressure regulator.
Do not kink or damage the flexible metal tubing when
moving the range.
Rigid pipe connection:
The rigid pipe connection
requires a combination
of pipe
fittings to obtain an in-line connection to the range. The rigid
pipe must be level with the range connection.
All strains must
be removed from the supply and fuel lines so range will be
level and in line.
Must include a shutoff valve:
The supply line must be equipped with a manual shutoff
valve. This valve should be located in the same room but
external to the range. It should be in a location that allows
ease of opening and closing. Do not block access to shutoff
valve. The valve is for turning on or shutting off gas to the
range.
B
c'
A. Gas supply line
B. Shutoff valve "open" position
C. Torange
Gas Pressure Regulator
The gas pressure regulator supplied with this range must be
used. The inlet pressure to the regulator should be as follows for
proper operation:
Natural gas:
Minimum pressure: 5" WCP
Maximum pressure: 14" WCP
LP gas:
Minimum pressure: 11" WCP
Maximum pressure: 14" WCP
Contact local gas supplier if you are not sure about the inlet
pressure.
Burner Input Requirements
Input ratings shown on the model/serial rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a
rate of 4% for each 1,000 ft (304.8 m) above sea level (not
applicable for Canada).
Gas Supply Pressure Testing
Line pressure testing above 1/2psi gauge (14" WCP)
The range and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2psi (3.5 kPa).
Line pressure testing at 1/2psi gauge (14" WCP) or lower
The range must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2psi (3.5 kPa).
The cooktop sides of the slide-in range fit over the cutout edge of
your countertop.
If you have a square finish (flat) countertop and the opening width
is 30" (76.2 cm), no countertop
preparation is required.
Formed front-edged
countertops
must have molded edge
shaved flat %" (1.0 cm) from each front corner of opening.
Tile countertops
may need trim cut back %" (1.0 cm) from each
front corner and/or rounded edge flattened.
If countertop
opening width is greater than 30" (76.2 cm), adjust
the %" (1.0 cm) dimension.
Countertop
must be level. Place level on countertop,
first side to
side, then front to back. If countertop
is not level, range will not
be level. Range must be level for satisfactory
baking conditions.