Page 1
Installation Instructions personnel must perform all other operations. When working heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit, and other safety precautions that may apply. Follow all safety codes. In the United States, follow...
Page 2
Table 1 - KGANP5201VSP Contents COMPONENT DESCRIPTION NUMBER ELECTRICAL S HOCK, F IRE OR EXPLOSION 616166-629 1 PCS CARTON HAZARD 319965-445 1 PCS LABEL, SHIPPING 320069-602 2 PCS TAPE Failure t o follow this warning could result in personal 326269-701...
Page 3
HOTSURFACE IGNITER MANUALRESET GASBURNER ROLLOUT SWITCH ELECTRICALJUNCTION BOX( REPRESENTATIVE DRAWING ONLY, SOME MODELS VARY IN APPEARANCE Al1408 Fig. 1 - Component Location MANIFOLD/ORIFICE/BURNER REMOVAL 3. Support the manifold and remove the 4 screws that secure the manifold assembly to the burner box and set aside. 4.
Page 4
THiS APPLIANCE HAS BEEN CONVERTED TO USE PROPANE GAS FOR FUEL. REFER TO KIT iNSTRUCTiONS FOR CONVERSION PROCEDURES. USE PARTS SUPPLIED BY CARRIER CORPORATION AND iNSTALLED BY QUALiFiED PERSONNEL. SEE EXISTING RATING PLATE FOR APPLIANCE MODEL NO. AND iNPUT RATING.
1. Remove the 1/8-in. NPT pipe plug from the gas valve inlet pressure tap. NOTE: Use pipe dope approved for use with Propane Gas. NOTE: Tighten all fittings and the Low Gas Pressure Switch > with a small wrench. Do not over-tighten, check for gas leaks after gas supply has been turned on.
For larger casing when Vent Pipe does not pass across casing. All Sizes switch contacts must point toward the Cell Panel. Black Iron Street 90 can be used at Valve Inlet instead of Brass Street Brass Street D'EQUIPEMENT D'OPERATION Toute erreur de cfiblage peut _tre une source de danger et de panne.
Page 8
RISQUE D'EXPLOSION ET D'INCENDIE 24 VAC Le fait de ne pas suivre cet avertissement pourrait entrai'nerdes Outside Air Thermistor_ HUM Output dommages corporels et / ou la mort. (O.5 AMP _[ SW4 Ne jamais examiner pour les fuites de gaz avec une flamme _/F_ Crflntin u;_2pFan_ vive.
Page 9
SET GAS INPUT RATE crease manifold pressure or clockwise to increase manifold pressure. 12. Turn rotary adjustment switch no more than one click per second until you obtain the required manifold pressure. UNIT DAMAGE HAZARD Failure to follow this caution result in gas valve...
THiSFURNACEWAS CONVERTED CE GENC:RATEUR D'NR CHAUD A €:TI_ TO PROPANEGAS CONVERTiLE POUR (DAY-MONTH-YEAR) (JOUR-MOIS-ANNI_E) KiT NO.: KGANP5201VSP DE L'ENSEMBLE N°.: KGANP5201VSP PAR: (Name and address of organization making this conversion), (Nora et adresse I'organisme a effectu6 [a conversion),...
Page 11
SECTION Table 3 - Variable Speed Condensing Furnaces LE FEU, L'EXPLOSION, CHOC ELECTRIQUE, MODEL NUMBERS BEGINNING WITH: ET MONOXYDE DE CARBONE 59TN6 986T EMPOISONNER PG96V T Cette trousse de conversion doit _tre install_e par un servie INSTALLATION d'entretien qualifid, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l'autorit_...
Page 13
2% for each 1000 ft. (305m) above sea meveL mnCanada the input rating must be derated by 5% for altitudes of 2000 ft. (610m) to 4.500ft. (1372m) above sea meveL FUELUSED: PROPANEGAS NLETPRESSURE(min-max): 11.0-13.61n.wc KiT NO.: KGANP5201VSP (SUPERSEDES: NONE) ALTITUDE OF iNSTALLATiON (FT. ABOVE SEA LEVEL) U.S.A.
REINSTALL BURNER ASSEMBLY To reinstall burner assembly: 1. Attach flame sensor to burner assembly. ELECTRICAL SHOCK, FIRE EXPLOSION 2. Insert one-piece burner in slot on sides of burner box and HAZARD slide burner back in place. Failure to follow this warning could result in personal...
Page 15
(Ifthe vent pipe passes between the inducer and burner assembly, For larger casing when Vent Pipe does not pass across casing. All Sizes orthe furnace isa143/16-in. (360 ram) wide casing, install the switch contacts must point toward the Cell Panel. Black Iron Street...
Page 16
6. Jumper R-W/W1 and R-W2 thermostat connections control. 7. When main burners ignite, confirm inlet gas pressure D'EQUIPEMENT D'OPERATION between ll.0-in. W.C. and 13.6-in. W.C. 8. Remove jumper across R-W/WI and R-W2 thermostat Toute erreur de cfiblage peut _tre une source de danger et de connections to terminate call for heat.
Page 17
1.Be sure m ain g as and electric supplies to furnace are off. 12. Remove jumper across R, Wl, and W2 after high-heat justment to terminate call for heat. 2. Remove l/8-in. (3 ram) pipe plug from manifold pressure tap on downstream side of gas valve.
Page 18
SECTION Table 4 - Non-condensing Furnaces FIRE, EXPLOSION, ELECTRICAL SHOCK MODEL NUMBERS BEGINNING WITH: HAZARD 58CVA 315AAV 58CVX 315JAV Failure to follow this warning could result in personal iniury, death or property damage. PG8MVA PG8JVA supply MUST shut before disconnecting INSTALLATION electrical power...
Page 19
3. Squeeze the sides of the device, if necessary, to remove Clp, Harness from the heat exchanger. Burner Assy 4. Re-install screw in hole underneath heat exchanger inlet. NOTE: It is very IMPORTANT to reinstall the NOx bracket mounting screw. umer Support Assy...
Page 20
THiS APPLIANCE HAS BEEN CONVERTED TO USE PROPANE GAS FOR FUEL, REFER TO KiT iNSTRUCTiONS FOR CONVERSION PROCEDURES. USE PARTS SUPPLIED BY CARRIER CORPORATION AND iNSTALLED BY QUALiFiED PERSONNEL. SEE EXiSTiNG RATING PLATE FOR APPLIANCE MODEL NO. AND iNPUT RATING.
Page 21
1-7/8 (47.6 mm) FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal iniury, death or property damage. supply MUST shut before disconnecting electrical power and proceeding with conversion. A05026 Fig. 41 - Igniter Position - Top View t¾2"...
Page 22
TWO-STAGE 9. With a back-up wrench on the inlet boss of the gas valve, finish tightening the gas pipe to the gas valve. ON/OFF 10. Turn gas on at electric switch on gas valve. Regulator Seal Cap INSTALL PRESSURE SWITCH Regulator Adjustment 1/2"NPT Regulator...
7. Connect orange wire from Gas Pressure Switch to the terminal on the Low Heat Pressure Switch. 8. Route orange wires along wire harness. If possible, secure FIRE AND EXPLOSION HAZARD with wire tie provided in kit. Failure CHECK INLET PRESSURE to follow this warning...
back-up w rench ontee when tightening gas inletpipe plug. (See F ig. 4 6.) ELECTRICAL SHOCK, FIRE EXPLOSION HAZARD 2" Brass Nipple Failure to follow this warning could result in personal Low Gas iniury, death or property damage. Pressure Switch Before installing, modifying,...
Page 25
TO PROPANEGAS CONVERTILE POUR (DAY-MONTH-YEAR) (JOUR-MOIS-ANNEE) KiT NO.: KGANP5201VSP DE L'ENSEMBLE N°.: KGANP5201VSP PAR: (Name and address of organization making this conversion), (Nora et adresse de ['organisme qui a effectu_, la conversion), which accepts the responsibRRy that this conversion qui accepte |' entri_re responsabRitO de la conversion.
Page 26
Copyright 2012 CAC / BDP • 7310 W. Morris St. • Indianapolis, IN 46231 Edition Date: 08/12 Catalo_ No: AG-KGANPVSP-04 Replaces: AG KGANPVSP Manufacturer reserves the right to change, at any time, specification8 and design8 without notice and without obligations,...