Design Information
PRODUCT DIMENSIONS
ZVC36
The custom canopg must be sized to fit the insert
sleeve. Construct
the canopg with an opening
that is:
26'M/x
13-3/16"D
The opening must be constructed
of :3/4" thick
material to allow the sleeve locking clips to
engage.
The Supplied Liner
34-1/2"
21-1/4"
/'
I_
side
,,'
The stainless steel liner is shipped with each hood
insert. This non-combustible
liner protects the
underside of the canopy.
Custom Liner
If you are not using the supplied liner, you may
construct
a custom non-combustible
liner. Use the
supplied liner as a template.
The opening
must be
26"W x 13-3/16"D.
:3//4" thick material must
surround
the opening to allow the sleeve locking
clips to engage. The insert sleeve inside the cabinet
should be positioned
1/2" from the rear wall so
that the center of the 8" duct is 5-1/2" from the
rear wall.
Dimensions
and Specifications
(in inches)
Outside Dimensions
27-1/2"
"1
The Insert Sleeve
14"
112"
!2"
25 -3/4" -
112"
The bottom edge of the insert sleeve has a 7/8"
wide flange on the sides and a 1/2" wide flange
on the front and back.
Remote Location for the Control
The control may be removed from the hood
and installed into a wall or countertop.
A 30-ft.
length of wire is supplied to accommodate
most
installations.
A blanking plate covers the opening
when the controls are removed.
The overall size of the control
is 4-1/4" wide and
2-1/4" deep.
3-11116"
1-11/16"
Control cutout
We recommend
that the cutout in granite or other
hard surfaces be made before the countertop
is
installed.