GE LP33 Series 80 User Manual page 27

Lp33 series 80 & 100kva / 208vac ul / s1
Table of Contents

Advertisement

Home\Meter
UTILITY
f
L1
L2
L3
BYPASS FREE
Home\Meter
INVERTER
f
L1
L2
L3
T
SYNCHRONIZED
Home\Meter
MODULE LOAD
L1
:
120 V
L2
:
120 V
L3
:
120 V
LOAD ON INVERTER
Home\Meter
COUNTERS
Bypass utility failure
Rectifier utility failure
Overloads
InvOperTime [h]
UPSOperTime [h]
Home\Meter
UTILITY
NUMBER OF FAST TRANSIENTS
<2ms
>2ms
25
20
ECO MODE RATE
Modifications reserved
OPM_LPS_3UO_80K_M10_1US_V010.doc
60 Hz
120 V
120 V
120 V
60 Hz
120 V
120 V
120 V
OK
139.0 A
50 %
139.0 A
50 %
139.0 A
50 %
:
53
:
35
:
15
:
2135
:
3125
>5ms
>10ms
7
5
=
70 %
Bypass utility data screen
f
The frequency of the utility.
L1
L2
3-phase utility voltage PHASE /NEUTRAL.
L3
Bypass
Bypass status: FREE / LOCKED.
Inverter data screen
f
The output frequency of the Inverter.
L1
L2
3-phase output voltage PHASE/NEUTRAL.
L3
T
The temperature of the inverter bridge (OK / MAX).
The synchronization status of the inverter with respect to
utility (Synchronized / Not Synchronized).
Module load screen
... V
Output voltage PHASE/NEUTRAL for each phase.
... A
The output current as RMS values (RPA: value for
each UPS).
... %
The output load as percentage (RPA: value for each
UPS).
The source of the power supplied to the load.
Statistics screen
The total number of minor utility faults (bypass utility out of
tolerance faults).
The total number of times a gap of utility in the rectifier has
been reordered.
The total number of detected output overloads.
The total operating time for the Inverter (in hours).
The total operating time for the UPS (in hours).
ECO Mode statistic screen
This screen is enabled only for a single UPS, not for an RPA
Parallel System.
The number of fast transients occurred on the bypass
utility in the last seven days.
The statistic evaluation in % (100= good; 0= bad) of the
utility, for the ECO mode operation.
Page 27/66
User Manual LP33 Series 80 & 100 UL S1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lp33 100