Haier AB092XCERA Operation And Installation Manual
Haier AB092XCERA Operation And Installation Manual

Haier AB092XCERA Operation And Installation Manual

Haier multi-split series room air conditioner operation & installation manual
Hide thumbs Also See for AB092XCERA:

Advertisement

Quick Links

R410A MULTI SPLIT SERIES ROOM AIR CONDITIONER
CASSETTE TYPE INDOOR UNITS
OPERATION & INSTALLATION MANUAL
No.0010577258
A
Please read this manual carefully before usingthis air conditioner.
Please keep this manual safely for future use.
AB092XCERA
AB122XCERA
AB142XCERA
AB182XCERA

Advertisement

Table of Contents
loading

Summary of Contents for Haier AB092XCERA

  • Page 1 R410A MULTI SPLIT SERIES ROOM AIR CONDITIONER CASSETTE TYPE INDOOR UNITS OPERATION & INSTALLATION MANUAL No.0010577258 Please read this manual carefully before usingthis air conditioner. Please keep this manual safely for future use. AB092XCERA AB122XCERA AB142XCERA AB182XCERA...
  • Page 2: Table Of Contents

    Contents Cautions ... Main Points of Operation ... Parts and Functions ... Safety Cautions ... Maintenance ... When Trouble Happens ... Customer Need-to-know ... Installation Procedures ... Instructions to installation ... Trouble Shooting... 12-17 18-19 20-22...
  • Page 3: Cautions

    Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier. Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
  • Page 4 5. The power cable and connecting cable are self-provided. The requirement of the communication cable: Model AB092XCERA H05RN-F 3G (1-2.5)mm AB122XCERA AB142XCERA H05RN-F 3G (1-2.5)mm AB182XCERA H05RN-F 3G (1-2.5)mm 6. The waste battery shall be disposed properly. 7. The indoor unit installation height is at least 2.5m.
  • Page 5: Main Points Of Operation

    There is a telecommunication interface for remote control on the control panel of the indoor unit. After the peripheral equipment have been installed in accordance with the instruction manual of the selected remote control detector, the air conditioner will be computerized and controlled from a far- away place.
  • Page 6 Setting Method: When the remote controller is on (excluding timer mode and fan mode),press the ìsleepingî button on the remote controller 10 times within 5 seconds,and after the buzzer rings 4 times, the air conditioner will enter the state of power failure compenstation.
  • Page 7: Parts And Functions

    Parts and Functions Air Inlet Grille Air Filter (Inside of the Inlet Grille) Swing louver (Air flow direction can be adjusted by using the SWING button on the remote controller) Operating Control Panel...
  • Page 8: Safety Cautions

    Safety Cautions Carefully read the following information in order to operate the air conditioner correctly. Below are listed four kinds of Safety Cautions and Suggestions: WARNING: Incorrect operations may result in severe consequences of death or serious injures. Incorrect operations may result in injures or machine damages; in some cases may CAUTION : cause serious consequences.
  • Page 9 Use discharge pipe correctly to ensure efficient discharge. In correct pipe usage may cause water leaking. Air conditioner canít be be installed in the environment with inflammable gases. The inflammable gases near to air conditioner may cause fire hazard. Installed electrical-leaking circuit breaker.
  • Page 10: Maintenance

    Maintenance Clean the unit Turn off the power supply switch The 4 fixed bolts must be loosed as shown in the figure by arrow if they are bolts, the method is that: push the blots inward till to another edge. Clean the air filter Clean the air filter with water or vacuum cleaner.
  • Page 11 Stop operation and turn off the power supply switch .Electric power is consumed even the air conditioner is in stop. Clean the air filter, indoor unit and outdoor unit,and cover the unit with dustcoat.
  • Page 12: When Trouble Happens

    Insufficient cooling Sunlight direct into the room ? When the air conditioner does not operate properly after you have checked the above-mentioned items or when following phenomenon is observed,stop the operation of the air conditioner and contact your sales dealer.
  • Page 13: Customer Need-To-Know

    Customer Need-to-know Customer Need-to-know Please install the air conditioner according to the requirements specified in this manual to ensure the air conditioner work well. Be careful not to scratch the surface of the case during moving the air conditioner. Please keep the installation manual for future reference when maintenance and changing installation place.
  • Page 14: Installation Procedures

    Installation Procedures 1.Selection of Installation Place (1) Place above the ceiling where have enough space to arrange the unit. (2) Place where the drainage pipe can be arranged well. (3) Place where inlet and outlet air of indoor and outdoor unit will not be blocked. (4) Do not expose the unit to the place with heavy oil or moisture (e.g.kitchen and workshop).
  • Page 15: Installation Of Indoor Unit

    Installation Procedures (3) Install a suspending bolt To support the unit weight ,anchor bolt should be used in the case of already exists ceiling. Fow new ceiling, use flush-in type bolt, built-in type bolt or parts pretared in the field. Before going on installing, adjust space to ceiling.
  • Page 16: Installation Of Water Drainage Pipe

    Installation Procedures 4. Installation of water drainage pipe (1) Install water drainage pipe Pipe diameter shall be equal or larger than that of connecting pipe (Pipe of polythene; size: 25mm; O.D.: 32mm ) Drainpipe should be short, with a downward slope at least 1/100 to prevent air bag from forming. If downward slope of drainpipe cannot be made,lifting pipe shall be installed.
  • Page 17 Installation Procedures 6. Installation of Ornament Panel Install ornament panel on indoor unit (1) Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check that the dimension of the ceiling opening is correct. Take off the lever gauge before install the ornament panel.
  • Page 18: Piping Connection

    Installation Procedures 7. Piping Connection Flare connection AB092XCERA Indoor AB122XCERA Unit Flare connection AB142XCERA AB182XCERA Indoor Unit To gas pipe (1) Dimension of connecting pipe AB092XCERA AB122XCERA AB142XCERA AB182XCERA Fit the nut on and fasten (2) The maximum length and drop height of connecting pipe The maximum length is 20m The maximum drop height is 10m.
  • Page 19 Installation Procedures 8.Electrical Wiring Wiring methods: 1 Wiring method of ring terminal For connecting line which end is a ring,its wiring method as shown in the right figure: remove wiring screw and pass it through the end ring of connecting line,then connect it to the terminal block and tighten screw.
  • Page 20: Instructions To Installation

    Instructions to installation 9. Indoor unit communication addresses setting CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK. 1.There are two methods to set the communication address A. Use the remote controller(default status in first installation). B. Use dip switches on the indoor unit PCB. 2.
  • Page 21: Instructions To Installation

    Instructions to installation SW01 1 2 3 4 5 6 7 8 4. How to check the addresses? When finish all the above works, please power off and power on again to the whole system but set all the indoor units in STANDBY. Then continously press the emergency switch until you hear the buzzer sound 5 times(Pi Pi Pi Pi Pi), and then the TIMER LED board will show the address of this indoor unit.
  • Page 22: Trouble Shooting

    When the air conditoner is started, when the compressor starts or stops during operation or when the air conditioner is stopped,it som- etimes sounds ì Bi- Bi-î or ìGodo-Godoî. It is the flowing sound of the refrigerant , not a malfunction.
  • Page 23 During heating,indoor fan is still running even unit is stopped. Please check the following things about your air conditioner before making a service call. Is the power supply switch on ? Power supply switch is not in ON position.
  • Page 24 Trouble Shooting TROUBLE SHOOTING Faulty temperature sensor Tai Faulty temperature sensor Tc1 Faulty temperature sensor Tc2 Faulty temperature sensor Tm Faulty EEPROM on indoor unit PCB Abnormal communication between indoor and outdoor unit Abnormal communication between wired controller and indoor unit PCB Drainage system abnormal Indoor unit address repeated Central control address repeated...
  • Page 25 HAIER GROUP Qingdao Haier Air Conditioner Electric Co., Ltd. Address: Haier Garden, Qianwangang Road, Economic Development Zone, Qingdao, Shandong 266555, P.R.China Web Site: http://www.haier.com...