Temperature And Pressure Relief Valve - American Water Heater Gas Water Heater Installation Instructions And Use & Care Manual

Gas water heater with the flame guard safety system
Hide thumbs Also See for Gas Water Heater:
Table of Contents

Advertisement

Temperature and Pressure
Relief Valve
Explosion Hazard
If the temperature and pressure relief
valve is dripping or leaking, have a
qualified service technician replace it.
Do not plug valve.
Do not remove valve.
Failure to follow these instructions can
result in death or explosion.
Figure 15A
Temperature and Pressure
Relief Valve Installation
For protection against excessive pressures and
temperatures, a temperature and pressure relief valve must
be installed in the opening marked "T & P RELIEF VALVE"
(see Figure 15A). This valve must be design certified by
a nationally recognized testing laboratory that maintains
periodic inspection of the production of listed equipment or
materials as meeting the requirements for Relief Valves and
Automatic Shut-off Devices for Hot Water Supply Systems,
ANSI Z21.22. The function of the temperature and pressure
relief valve is to discharge water in large quantities in the
event of excessive temperature or pressure developing
in the water heater. The valve's relief pressure must not
exceed the working pressure of the water heater as stated
on the data plate.
Important: Only a new temperature and pressure relief
valve should be used with your water heater. Do not use an
old or existing valve as it may be damaged or not adequate
for the working pressure of the new water heater. Do not
place any valve between the relief valve and the tank.
14
Discharge line 3/4" minimum
Do not cap or plug.
6" maximum
The Temperature & Pressure Relief Valve:
Must not be in contact with any electrical part.
Must be connected to an adequate discharge line.
Must not be rated higher than the working pressure
shown on the data plate of the water heater.
The Discharge Line:
Must not be smaller than the pipe size of the relief
valve or have any reducing coupling installed in the
discharge line.
Must not be capped, blocked, plugged or contain any
valve between the relief valve and the end of the dis-
charge line.
Must terminate a maximum of six inches above a floor
drain or external to the building.
Must be capable of withstanding 250°F (121°C) without
distortion.
Must be installed to allow complete drainage of both
the valve and discharge line
T&P Valve and Pipe Insulation
1. Locate the T&P Valve on the water heater.
2. Locate the slit running the length of the insulation.
3
Spread this slit open and slip it over the T&P Valve. See
Figure 15B. Apply gentle pressure to the insulation to
ensure it is fully seated on the T&P Valve. Once sealed
secure the insulation with a section of tape.
IMPORTANT: The insulation or tape should not block
or cover the T&P drain opening. Also the insulation or
tape should not block or hinder access to the T&P valve
manual relief lever.
4.
Next locate the hot water (outlet) & cold water (inlet)
pipes to the water heater.
5. Select one of the sections of pipe insulation and locate the
slit that runs the length of the insulation.
6. Spread the slit open at the base of the insulation and slip
it over the cold water (inlet) pipe. Apply gentle
pressure along the length of the insulation to ensure it is
fully seated around the cold water pipe. Also ensure that
the base of insulation is flush with the water heater. Once
seated secure the insulation with a section of tape.
7. Repeat steps 5 through 6 for the hot water (outlet) pipe.
Figure 15B
T&P Valve and Pipe Insulation
Manual Relief Lever
T&P Valve
T&P Valve
Drain Line
(Some Models)
T&P Insulation