MODEL NUMBER
MODEL RATING
VA/W
DIMENSIONS: in (mm)
Unit
W x D x H
Shipping
W x D x H
WEIGHT: lbs (kg)
Unit
Shipping
INPUT AC PARAMETERS
Voltage Range (typical)
100% - 70% Loading
70% - 30% Loading
30% - 0% Loading
Frequency
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles
Voltage
Frequency
Waveform
Main Mode Overload
BATTERY PARAMETERS
Type
Qty. x Voltage x Rating
Batt. Mfg./ Part #
Back-up Time
Recharge Time
ENVIROMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Safety
RFI/EMI
Immunity
SPECIFICATIONS
GXT1000RT-120
1000 / 700
7.0 x 19.3 x 16.9
(177 x 522 x 430)
13.38 x 26.0 x 22.25
(340 x 660 x 565)
51.9 (23.6)
59.0 (26.8)
120 VAC nominal; variable based upon output load
80-83 VAC to 134-138 VAC
70-73 VAC to 134-138 VAC
60-62 VAC to 134-138 VAC
48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing
6 ft. detached,
w/ NEMA 5-15 plug
(8) NEMA 5-15R
100/110/120/127 (switch selectable) VAC; ±3%
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Valve-regulated, nonspillable, lead acid
3 x 12V x 7 or 7.2 AH
CSB GP1270F2 or Panasonic LC-R127R2CH1
See Typical Battery Discharge Curves
5 Hours to 95% capacity after
full discharge into 100% load
+32° F to +104° F (0° C to +40° C)
+5° F to +122 °F (-15° C to +50° C)
0% to 95%, non-condensing
Up to10,000 ft. (3000 m) at 40° C without derating
50,000 ft. (15,000 m) maximum
FCC Part 15, Subpart B, Class A
24
GXT1000RTE-120
13.38 x 26.0 x 22.25
w/ NEMA 5-15 plug
50 Hz or 60Hz
Sinewave
10 Hours to 95% capacity after
full discharge into 100% load
<45 dBA, at 1 meter
UL 1778, c-UL Listed
IEEE 587 Category A
1000 / 700
7.0 x 19.3 x 16.9
(177 x 522 x 430)
(340 x 660 x 565)
68.4 (31.1)
75.5 (34.3)
6 ft. detached,
(8) NEMA 5-15R
6 x 12V x 7 AH