Wiring; Heat Recovery Ventilator (Hrv) And Energy Recovery Ventilator (Erv) Connections; Digital Fan Timer - Honeywell Perfect Window HR150 200 Product Data

Perfect window fresh air ventilation systems
Table of Contents

Advertisement

WIRING

CAUTION: Electrical shock hazard.
Can cause personal injury.
Be sure ventilator is correctly grounded. Confirm polarity of power line switched with safety (disconnect)
switch when cleaning or servicing unit.
IMPORTANT
The hot line (black) is the correct line to switch. See Fig. 19. To confirm correct polarity, use voltmeter or test lamp to
verify there is no power after the switch when the door is open. Check between that point and ground (on cabinet). This
process must be used because occasionally some dwellings are incorrectly wired.
CAUTION: Electrical hazard.
Can cause equipment damage.
Disconnect HRV/ERV from power source before connecting or disconnecting digital fan timer or other
device to HRV/ERV high-speed override terminals.
IMPORTANT
Do not connect external power sources to the highspeed override terminals.

Heat Recovery Ventilator (HRV) and Energy Recovery Ventilator (ERV) Connections

The connector is a three-prong, 120 Vac plug with ground. If further wiring is required, Honeywell recommends
that a licensed electrician make all electrical connections. It is very important that the unit be correctly grounded.

Digital Fan Timer

HIGH SPEED
STATUS LIGHTS
SELECT BUTTON
INITIATES HIGH
SPEED VENTILATION
FOR 20, 40 OR 60
MINUTES
Fig. 10.
Digital fan timer lights and Select Button.
12
Mount digital fan timer in a full or one-half depth
electrical box in the living space. See Fig 10.
Press and release the Select Button to activate high
speed on the ventilator. Change between 20-, 40-, and
60-minute override times by pressing and releasing
YELLOW
the Select Button.
The status light will dim after 10 seconds of run time.
RED
The status light will flash during the last 5 minutes of
GREEN
override. All timers connected to the unit will illuminate
for the duration of the override.
Set the lockout mode by holding the Select Button for
M29806
5 seconds. Unlock by holding for 5 seconds.
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12