Kohler PW 5000/TP User Manual page 25

Hide thumbs Also See for PW 5000/TP:
Table of Contents

Advertisement

Fuse A
Rectifier
FA3
Battery
(F1)
Fuse
UPS Cabinet
SINGLE INPUT FEED
Power (kVA)
Fuse A (Agl/CB) (A)
10
15
20
25
30
40
50
Notes:
1.
Fuse and Cable recommendations to IEC 60950-1:2001.
2.
The fuse and cable rating details in the above tables are a recommendation only.
3.
The UPS must be installed to prescribed IEC or local regulations.
4.
External DC Cables and Battery fuses are bespoke to the installation.
UPS412-01-01 Kohler PW 5000/TP User Manual Dated 17-11-11
INPUT MAINS SUPPLY
L1
L2
L3
N
A
A
A
A
IL1
IL2
IL3
IN
PE1
Bypass Links
Input
FA1
Fuse
FA2
Inverter
Static
Switch
Output
IA2
(Parallel)
Switch
3L1
D
3 x 20
3 x 32
3 x 40
3 x 40
3 x 63
3 x 80
3 x 80
Figure 3.8 Single input feed - power connection diagram
PE
A
2L1
2L2
2L3
Bypass
Fuse
Maintenance
Bypass
IA1
Switch
3L2
3L3
3N
PE3
D
D
D
D
OUTPUT (LOAD) SUPPLY
Cable A (mm²)
5 x 2.5
5 x 4.0
5 x 6.0
5 x 6.0
5 x 10
5 x 25
5 x 25
3: Installation
2N
PE2
Cable D (mm²)
5 x 2.5
5 x 4.0
5 x 6.0
5 x 6.0
5 x 10
5 x 25
5 x 25
3-11

Advertisement

Table of Contents
loading

Table of Contents