Kohler PW 5000/TP User Manual page 21

Hide thumbs Also See for PW 5000/TP:
Table of Contents

Advertisement

SINGLE INPUT FEED (standard)
Fuse A
Cable A
FA1
Rectifier
FA4
FA3
(F1)
EXTERNAL
BATTERY
CABINET
Int. Batts.
(option)
SINGLE INPUT FEED
Power (kVA)
10
15
20
25
30
40
50
DUAL INPUT FEED
Power (kVA)
(Agl/CB) (A)
10
15
20
25
30
40
50
Notes:
1.
Fuse and Cable recommendations to IEC 60950-1:2001
2.
The fuse and cable rating details in the above tables are a recommendation only.
3.
The UPS must be installed to prescribed IEC or local regulations.
4.
External DC Cables and Battery fuses are bespoke to the installation.
UPS412-01-01 Kohler PW 5000/TP User Manual Dated 17-11-11
FA2
Inverter
Static Switch
Output
Maint.
IA2
IA1
Switch
Bypass
Cable D
Load
Fuse A (Agl/CB) (A)
3 x 20
3 x 32
3 x 40
3 x 40
3 x 63
3 x 80
3 x 80
Fuse B
Cable B (mm²)
3 x 20
5 x 2.5
3 x 32
5 x 4.0
3 x 40
5 x 6.0
3 x 40
5 x 6.0
3 x 63
5 x 10
3 x 80
5 x 25
3 x 80
5 x 25
Figure 3.4 Kohler PW 5000/TP fuse & cable rating
DUAL INPUT FEED
Mains (3x380/220V,
3x400/230V,
3x415/240V)
Fuse B
Cable B
FA1
Rectifier
FA4
Inverter
FA3
(F1)
EXTERNAL
Output
BATTERY
Switch
CABINET
Int. Batts.
(option)
Cable A (mm²)
5 x 2.5
5 x 4.0
5 x 6.0
5 x 6.0
5 x 10
5 x 25
5 x 25
Fuse C
Cable C (mm²)
(Agl/CB) (A)
3 x 20
5 x 2.5
3 x 32
5 x 4.0
3 x 40
5 x 6.0
3 x 40
5 x 6.0
3 x 63
5 x 10
3 x 80
5 x 25
3 x 80
5 x 25
3: Installation
Fuse C
Cable C
FA2
Static Switch
Maint.
IA2
IA1
Bypass
Cable D
Load
Cable D (mm²)
5 x 2.5
5 x 4.0
5 x 6.0
5 x 6.0
5 x 10
5 x 25
5 x 25
Cable D (mm²)
5 x 2.5
5 x 4.0
5 x 6.0
5 x 6.0
5 x 10
5 x 25
5 x 25