Download Print this page
Greenheck Steel Airfoil Blades SMD-301M Specification Sheet
Greenheck Steel Airfoil Blades SMD-301M Specification Sheet

Greenheck Steel Airfoil Blades SMD-301M Specification Sheet

Smoke dampers steel airfoil blades ul 555s leakage class i

Advertisement

Quick Links

Application
Model SMD-301 is a leakage rated smoke damper with extremely
low leakage. The SMD-301 serves the function of both a control
damper and smoke damper. High strength airfoil blades insure
lowest resistance to airflow in HVAC systems with velocities to
3000 fpm (15.2m/s) and 4 in. wg (1.0 kPa) Model SMD-301 may be
installed vertically (with blades running horizontal) or horizontally
and is rated for airflow and leakage in either direction.
UL555S Leakage Rating
Leakage Class:
Operational Rating
Maximum Velocity:
Maximum Pressure:
Maximum Temperature: 350ºF (177ºC) depending on
Standard Construction
Frame:
Blades:
Seals:
Linkage:
Axles:
Bearings:
Size Limitations:
Minimum Size:
Maximum Size:
Single Section:
Multiple Section:
Optional Features:
• Galvanized steel sleeves.
• Stainless steel bearings
• OCI (Open closed indication switches)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• Transitions (R, C, O)
• POC retaining angles
• Momentary Switch
• Smoke detectors
• Sealed transitions and sleeves
• Fail open
I
3000 fpm (15.2 m/s)
4 in. wg (1 kPa)
actuator
5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes less
than 17 in. (432mm) high to
maximize free area and
performance.
Double skin airfoil shape of
galvanized steel with full length
structural reinforcement. 14 ga.
(2 mm) equivalent thickness.
Extruded silicone rubber blade
seals. Flexible stainless steel jamb
seals.
Concealed in jamb.
/
in. (13mm) dia. plated steel.
1
2
Bronze sleeve type.
8 in. W x 6 in. H
(203mm W x 152mm H)
32 in. W x 50 in. H
(813mm W x 1270mm H)
128 in. W x 100 in. H
(3251mm W x 2540mm H) or
256 in. W x 50 in. H
(6502mm W x 1270mm H)
Model SMD-301 meets the requirements for smoke
dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#2330-0981:104)
"UL CLASSIFIED (see complete marking on
product)"
"UL CLASSIFIED to Canadian safety standards
(see complete marking on product)"
Standard 555S (Listing #R13317)
Greenheck Fan Corporation certifies that the
model SMD-301 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Programs. The
R
AMCA Certified Ratings Seal applies to air
performance ratings only.
LH
W*
*W&H dimensions furnished approximately
Right hand drive is shown. Left hand drive is available upon request.
Damper also may be rotated 180° in the field for opposite side drive.
(Add sleeve thickness for overall sleeved damper dimension)
Installation instructions available at www.greenheck.com
SMD-301
Smoke Dampers
Steel Airfoil Blades
UL 555S Leakage Class I
RH
1
/
in. (6mm) undersize.
4
H*

Advertisement

loading

Summary of Contents for Greenheck Steel Airfoil Blades SMD-301M

  • Page 1 “UL CLASSIFIED to Canadian safety standards (see complete marking on product)” Standard 555S (Listing #R13317) Greenheck Fan Corporation certifies that the model SMD-301 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed...
  • Page 2: Pressure Drop Data

    Pressure Drop Data This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.
  • Page 3 0.67 0.87 4000 0.88 Greenheck Fan Corporation certifies that the model SMD-301 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs.
  • Page 4 0.29 0.42 4000 0.38 Greenheck Fan Corporation certifies that the model SMD-301 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs.
  • Page 5 1.48 2.14 4000 1.93 Greenheck Fan Corporation certifies that the model SMD-301 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs.
  • Page 6: Application Data

    Application Data Damper Sideplate and Sleeve Dimensional Data The drawings below illustrate the factory standard sideplate and sleeve mountings for the SMD-301. The standard "A" dimensions listed in the table provide adequate space for the mounting of actuators and controls. If space constraints are a problem the "A"...
  • Page 7: Specifications

    16 in. (406mm) approximately Min. except round and oval dimensions which are approximately TYPE C undersize. T s = (2)(Sleeve Thickness) 128 in. (2540mm) Copyright ©2006 Greenheck Fan Corporation SMD-301 Rev. 4 June 2006 32 in. (813mm) in. (6mm) undersize, in. (3mm)