Download Print this page

Greenheck AX Brochure page 62

Greenheck high performance axial fans brochure

Advertisement

AX 160-533 8 Blades
Page Header
Total
Pressure
Air density = 1.2 kg/m ³
Air density = 0.075 lbs/ft ³
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm
5
1170 (Bhp/kW)
19.2/14.3
32.5/24.3
870 (Bhp/kW)
7.90/5.90
13.4/9.98
950 (kW)
7.68
720 (kW)
3.34
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
104
104
Pitch Angle º
10
15
20
47.5/35.5
64.6/48.2
19.5/14.6
26.5/19.8
13.0
19.0
25.8
5.65
8.26
11.2
Impeller Diameter = 63.0 inches (1600 mm)
Outlet Velocity
Tip Speed
96
98
104
Volume
25
30
35
83.9/62.6
106/79.3
134/100
34.5/25.7
43.7/32.6
55.3/41.2
33.5
42.4
53.7
14.6
18.5
23.4
62
62
ft/min = cfm / 21.70
m/s = m ³ /s / 2.01
ft/min = rpm X 16.5
m/s = rpm X 5.03
102
103
103
101
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Inlet Sound
rpm
LwA
1170
+9
870
-
950
+3
720
-4
dBA
-2.5
-11.5
-8.5
-15.5

Advertisement