7. Installing refrigerant piping
10~20
30~50
Fig. 7-5
Caution:
Tighten the flare nut with a torque wrench in the specified method.
Overtightening will cause the flare nut to crack and it will cause refrigerant
leakage over a period of time.
C Apply refrigeration oil to the entire (Fig. 7-3) surface of the flared seat.
D Basically use flared nuts fitted to the body (commercially available flared nuts
may crack).

8. Installing drain piping

Type A
11
10
Type B
11
10
11
Fig. 8-1
1.5 to 2 m 25 cm
Fig. 8-2
6
(mm)
(mm)
11
Note:
A special flare nut (optional or attached to the indoor unit) is needed to
some indoor units.
Please refer to the installation manual of outdoor unit and indoor unit for
details.
E Section of connection (Fig. 7-4)
F Band 9
G Pipe covers 3 4 5 6
H Tighten
J Refrigerant piping
L Thermal insulation for refrigerant piping
► Use the following procedures for indoor connection part which indoor
unit is not connected. (Fig. 7-5)
(1) In order to prevent refrigerant leaks, make sure that the flare nuts are tightened
according to the specified torques* in Table 3.
* Refrigerant may also leak if the flare nuts are tightened more than the speci-
fied torques.
() In order to prevent condensation, install the pipe covers
with the supplied bands
.
9
Table 3
Diameters of branch box openings for
connecting indoor units (mm)
ø6.35
ø9.5
ø1.7
► Refrigerant charge:
Refer to the installation manual of the outdoor unit.
Use only R410A refrigerant (use of other refrigerants may cause troubles).
• To ensure that the drain piping has a down-gradient (greater than 1/100),
do not make traps or humps in piping.
• Install thermal insulation to prevent condensation dripping.
• Ensure that the horizontal length (not diagonal length) of drain piping does not
exceed 20 m. If the drain piping extends over a significant distance, install sup-
ports to ensure that the piping does not sag. Do not fit air bleed pipes under
any circumstances (water may exit from air bleed pipes).
• Do not fit odor traps at drain piping outlets.
• Install drain outlets in locations where odors will not present problems.
• Do not place drain piping directly in drains which may contain sulfurous gases.
• Drain piping may be installed in any direction provided the above requirements
are followed.
• Keep bends of attached drain hose to a maximum of 45°.
(1) Apply PVC adhesive (procure locally) to the drain connection on the branch
box and push the attached drain hose
go. (Fig. 8-1)
() Insert a hard PVC pipe (VP-16, procure locally) into the attached drain hose
and glue it together and fix it. (Fig. 8-1)
0
A VP-16 procured locally
B Thermal insulation
(3) Fit a band
to the attached drain hose
1
(4) Ensure that the drain piping down-gradient is greater than 1/100. (Fig. 8-)
C Supports
D Down-gradient greater than 1/100.
E Thermal insulation
Note:
The drain hose is available in either Type A or Type B.
The installation methods are different between Type A and Type B.
and fasten them
7 8
Tightening torque
(N·m)
13 ± 
30 ± 
50 ± 
onto the connection as far as it will
0
(Fig.8-1)
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pfc-ak51bcPac-ak52bcPac_ak32bcPac-ak31bc

Table of Contents