Download Print this page

Generac Power Systems MD500 Instruction Manual page 2

500 kw industrial diesel generator set

Advertisement

MD500
ENGINE SPECIFICATIONS
General
Make
EPA Emissions Compliance
EPA Emissions Reference
2 of 5
Cylinder #
Type
Displacement - L
Bore - mm (in.)
Stroke - mm (in.)
Compression Ratio
Intake Air Method
Cylinder Head Type
Piston Type
Connecting Rod Type
Engine Governing
Governor
Frequency Regulation (Steady State)
Lubrication System
Oil Pump Type
Oil Filter Type
Crankcase Capacity - L (Gal)
ALTERNATOR SPECIFICATIONS
Standard Model
Poles
Field Type
Insulation Class - Rotor
Insulation Class - Stator
Total Harmonic Distortion
Telephone Interference Factor (TIF)
Standard Excitation
Bearings
Coupling
Load Capacity - Standby
Prototype Short Circuit Test
CODES AND STANDARDS COMPLIANCE (WHERE APPLICABLE)
NFPA 99
NFPA 110
ISO 8528-5
ISO 1708A.5
ISO 3046
Rating Definitions:
Standby – Applicable for a varying emergency load for the duration of a utility power outage with no overload capability. (Max. load factor = 70%)
Prime – Applicable for supplying power to a varying load in lieu of utility for an unlimited amount of running time. (Max. load factor = 80%) A 10% overload capacity is available for 1 out of
every 12 hours.
Perkins
Stationary Emergency
See Emissions Data Sheet
6
In-Line
15.2
137 (5.39)
171 (6.73)
16.0:1
Turbocharged/Aftercooled
4 Valve
Aluminum
I-Beam Section
Electronic Isochronous
± 0.25%
Gear
Full-Flow Cartridge
60 (15.8)
WEG
4
Revolving
H
H
< 3%
< 50
Permanent Magnet
Single Sealed Cartridge
Direct, Flexible Disc
100%
Yes
BS5514
SAE J1349
DIN6271
IEEE C62.41 TESTING
NEMA ICS 1
application and engineering data
Cooling System
Cooling System Type
Water Pump
Fan Type
Fan Speed (rpm)
Fan Diameter mm (in.)
Coolant Heater Standard Wattage
Coolant Heater Standard Voltage
Fuel System
Fuel Type
Fuel Specifications
Fuel Filtering (microns)
Fuel Injection
Fuel Pump Type
Injector Type
Engine Type
Fuel Supply Line - mm (in.)
Fuel Return Line - mm (in.)
Engine Electrical System
System Voltage
Battery Charging Alternator
Battery Size (at 0ºC)
Battery Group
Battery Voltage
Ground Polarity
Voltage Regulator Type
Number of Sensed Phases
Regulation Accuracy (Steady State)
PARALLELING CONTROLS
Auto-Synchronization Process
Isochronous Load Sharing
Reverse Power Protection
Maximum Power Protection
Electrically Operated, Mechanically Held Paralleling Switch
Sync Check System
Independent On-Board Paralleling
Optional Programmable Logic Full Auto Back-Up Control (PLS)
Closed Recovery
Centrifugal Type, Belt-Driven
Pusher
1658 rpm
927 (36.5)
1500
120VAC
Ultra Low Sulfur Diesel #2
ASTM
Primary 10 - Secondary 2
Electronic
Engine Driven Gear
MEUI
Pre-Combustion
12.7 (½"NPT)
12.7 (½"NPT)
24VDC
70 Amps at 24V
1155 CCA
8D
(2) - 12VDC
Negative
Digital
All
± 1%

Advertisement

loading

This manual is also suitable for:

Md600