Mains connection
B
11. C onnect main cables and hide connected
wires behind LED Panel (B).
Installation Closing Panel (D)
1
D
12. I nstall Closing Panel (D) in-between troffer
and T-grid.
Remove LED protection
14. Tear off LED protection.
Connection 0-10V and MK10 dimmer (Optional)
EvoKit 0-10V wiring diagram
0-10V
DIM+
DIM-
16a. O ptional: For connection EvoKit 0-10V
input, use indicated connections on the
driver.
20130919
mains
2
1
13. F ixate panels and establish ground by
turning each fastener 90 degrees.
Installation Diffuser (E)
E
15. S lide Diffuser (E) under the tabs on one side
from either Panel and press diffuser (E) over
the tabs on opposite panel.
EvoKit MK10 wiring diagram
Dimmer
Class 1 Wiring
LINE 2
}
or Class 2 Circuit
NEUTRAL
0-10VDC
16b O ptional: For connection a dimmer to the
EvoKit Mark 10, use indicated connections
on the driver.
90
o
RISK OF FIRE OR ELECTRIC SHOCK
While installing the LED panel (B) and
Closing Panel (D), make sure the electrical
wiring is not clamped between panels.
Notice
Use 18 AWG Solid Copper Wire
Rated>=300V. Strip Wire 3/8"
In case the EvoKit MK10 277V is installed in
MK 10
combination with a dimmer, use a minimum
120V / 277V
of 2 EvoKits MK10 277V per dimmer.
WARNING
5