Specifications - Goodman 10.3 EER Specifications

Packaged air conditioner

Advertisement

S
PECIFICATIONS
Cooling Capacity
Total BTU/h
Sensible BTU/h ¹
EER ²
IPLV ³
Indoor Blowers (2)
Type
Wheel (D x W)
Indoor Nominal CFM
Horsepower
Evaporator Coil (1)
Face Area (ft²)
Rows Deep/ Fins per Inch
Tube Diameter - Material
Filter Size (ft²) / Quantity
Condenser Fans (2) / Coil (1)
Horsepower
Fan Diameter
Outdoor Nominal CFM
Face Area (ft²)
Rows Deep/ Fins per Inch
Tube Diameter - Material
Electrical Data
Voltage-Phase
Compressor RLA/ LRA
Indoor Blower FLA
Outdoor Blower FLA
Min. Circuit Ampacity
4
Max. Overcurrent Device
5
Operating Weight (lbs)
Ship Weight (lbs)
¹ Sensible capacity is gross, with no deduction for indoor motor heat
² BTU/Watt @ 80/ 67° F inside; 95° F outside air
³ IPLV = Integrated Part Load Valve
4
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
5
HACR breakers may be used in place of fuses up to 60 amps
SS-GPCC
PCC090-3A
PCC090-4A
86,000
86,000
63,600
63,600
10.3
10.3
10.7
10.7
Belt
Belt
12" x 12"
12" x 12"
3,000
3,000
11.2
11.2
3/ 16
3/ 16
⅜" - Copper
⅜" - Copper
––
––
25 x 25 x 2 / 3
25 x 25 x 2 / 3
½
½
24"
24"
5,500
5,500
15.6
15.6
2/ 21
2/ 21
⅜" - Copper
⅜" - Copper
208/230-3
460-3
12.5/ 88
5.9/ 44
4.2
2.0
2.6
1.3
38.1
18.2
60 amps
30 amps
980
980
1,000
1,000
www.goodmanmfg.com
P
S
RODUCT
PECIFICATIONS
PCC120-3A
PCC120-4A
116,000
116,000
85,000
85,000
10.3
10.3
10.7
10.7
Belt
Belt
12" x 15"
12" x 15"
3,800
3,800
3
3
14
14
3/ 16
3/ 16
⅜" - Copper
⅜" - Copper
16 x 25 x 2 / 3
16 x 25 x 2 / 3
20 x 25 x 2 / 3
20 x 25 x 2 / 3
½
½
24"
24"
6,400
6,400
23.8
23.8
2/ 21
2/ 21
⅜" - Copper
⅜" - Copper
208/230-3
460-3
17.4/ 123
6.8/ 49.5
8.4
4.2
2.6
1.3
54.5
22.5
70 amps
35 amps
1,270
1,270
1,290
1,290
3

Advertisement

loading

This manual is also suitable for: